Novus N322T Manual Download Page 1

 

The N322T is a 2-output digital electronic controller for heating and cooling applications. It is available 

with NTC thermistor input sensor, Pt100, Pt1000 or J/K/T type thermocouple. Sensor offset correction 

is provided. The 2 independent outputs can be used as control or alarm. 
Displays the 

Compressor Protection Function by Supply Voltage Monitoring

, important in the 

protection of compressors for refrigeration systems. 

SPECIFICATIONS 

INPUT SENSOR: 

The input sensor type can be chosen form the options below (specified when 

placing the order): 

 

NTC

 Thermistor, 10 k

 

@ 25 °C; range: –50 to 120 °C (-58 to 248 °F);               

Accuracy: 0.6 °C (1.1 °F), with original sensor; 
Sensor  interchangeability:  0.75  °C  (1.35  °F).  This  error  can  be  compensated  by  the 

offset

 

parameter in the controller. 

 

Pt100 (

= 0.00385); Range:  –50 to 300 °C (-58 to 572 °F); 

Accuracy: 0.7 °C (1.3 °F); IEC-751. 

 

Pt1000 (

= 0.00385);

 

Range: –200 to 530 °C (-328 to 986 °F); 

Accuracy: 0.7 °C (1.3° F); 

 

J, K or T thermocouple

 (IEC-584)

:

 

 

Type J

: Range: 0 to 600 ºC (32 to 1112 ºF); Accuracy: 3 ºC (5.4 ºF); 

 

Type K

: Range: -50 to 1000 ºC (-58 to 1832 ºF); Accuracy: 3 ºC (5.4 ºF); 

 

Type T

: Range: -50 to 400 ºC (-58 to 752 ºF); Accuracy: 3 ºC (5.4 ºF); 

Note

:  In the controller with NTC input, a 3 m-sensor cable is bundled with the  instrument. The 

cable can be extended up to 200 m.

 

WARM-UP:

 .......................................................................................................................... 15 minutes 

MEASUREMENT RESOLUTION:

 

From –19.9 to 199.9 º with NTC, Pt100 and Pt1000: ........................................................................... 0.1 
Elsewhere: ....................................................................................................................................... 1 

OUTPUT1:

 ......................................... Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive) 

 ................................................................................................... Optionally: Pulse, 5 Vdc, 25 mA max. 

OUTPUT2:

 .......................................................................................... Relay: 3 A / 250 Vac, SPST-NA 

POWER SUPPLY:

 ........................................ 100~240 Vac/dc (± 10 %) or 24 Vdc/ac (12~30 Vdc/ac) 

 ...................................................................... Mains frequency: 50~60 Hz. Power consumption: 5 VA 

Caution

: check the power supply specification before energizing the controller. 

DIMENSIONS

: .................................................................... Width x Height x Depth: 75 x 33 x 75 mm 

 ............................................................................................ Panel cut-out: 70 x 29 mm; Weight: 100 g 

ENVIRONMENT:

 .................................................... Operating temperature: 0 to 40 °C (32 to 122 °F) 

 .................................................................................. Storage temperature: -20 to 60 °C -4 to 140 °F) 
 .....................................................................................Relative humidity: 20 to 85 % non-condensing 

CASE:

 ..........................................Polycarbonate UL94 V-2; Protection: Front panel: IP65, Box: IP42 

 .............................................................................................................. Suitable wiring: Up to 4.0 mm² 

RS-485 digital communication; RTU MODBUS protocol (optional) 

Serial interface not isolated from input circuitry. 

Serial interface isolated from input circuitry, except in 24 V powered model.

 

 

 

 

 
 

ELECTRICAL WIRING 

Fig. 1

 below shows the controller connections to sensor, mains and outputs. 

 

Fig. 1

 - N322T terminals 

Pt100 with 3 conductors

: Terminals 11, 12 and 13 must have the same wire resistance for proper 

cable length compensation. For 2 wire Pt100, short circuit terminals 11 and 13. 

Recommendations for the installation 

 

Temperature sensor drivers must go through the plant separate system for drivers of control 

output and power supply if possible electroducts terrified. 

 

The  controller's  power  should  come  preferably  a  campus  network  for  instrumentation  or 

different from that used by phase control output. 

 

Installing  RC  filters  (47  R  and  100  nF,  series  combination)  is  strongly  recommended  at 

contactor coils or any other inductors. 

OPERATION 

The controller requires the internal parameters to be configured according to the intended use for 

the instrument. The parameters are organized in 4 groups or levels:  

Level 

Function 

Temperature measurement 

Setpoint adjustment / Voltage indication 

Configuration 

Calibration 

Upon  power-up,  the  N322T  display shows for  1 second  its  firmware version. This  information  is 

useful when consulting the factory. 
Then, the temperature measured by the sensor is shown on the display. This is the parameter level 

0

 (temperature measurement level). 

To access level 

1

, press 

 for 1 second until the “

SP

” message shows up. To go back to level 0, 

press 

 once more. 

To  access  level  2  of  parameters,  press 

  for  2  seconds  until  the  “

uNT

”  message  is  shown. 

Release the 

 

key to remain in this level. Each new pressing on the 

 key will advance to the 

next parameter in the level. At the end of the level, the controller returns to the first level (

0

).  

Use the 

 and 

 keys to alter a parameter value. 

Notes

:  1 

A parameter configuration is saved when the 

  

key is pressed to advance to the 

next parameter in the cycle. The configuration is stored in a non-volatile memory, 

retaining its value when the controller is de-energized. 

2

 

If  no  keyboard  activity  is  detected  for  over  20  seconds,  the  controller  saves  the 

current parameter value and returns to the measurement level. 

Level 1 – Setpoint Adjustment 

In this level only the Setpoint (

SP1 

and 

SP2

) parameters are available, alternating the names with 

their respective values. Adjust the desired temperature for each setpoint clicking on the 

 and 

 

keys.

 

Voltage

 - The screen voltage measurement. For values lower than 150 Vac and 

higher than 254 Vac presents the message 

0

Function available for model N322T-NTC-LVD. 

SP 

Set Point

 - Temperature adjustment for control. 

SP

 value is limited to the values 

programmed in 

SPL

 and 

SPk

 in the programming level. 

Level 2 – Configuration - Parameters configuration Level 

Contains  the  configuration  parameters  to  be  defined  by  the  user,  according  to  the  system’s 
requirements. Use 

 and 

 keys to set the value. The display alternates the parameter name 

and respective value. 

Unt 

Temperature

 

Unit

 - Selects display indication for degrees Celsius or Fahrenheit. 

0

 - Temperature in degrees Celsius 

1

 - Temperature in degrees Fahrenheit 

typ 

Input Type

 - Selects the input sensor type to be connected to the controller. 

Available only for thermocouple models, allowing selection of types J, K and T. 

0

 - Thermocouple type 

J

 

1

 - Thermocouple type 

K

 

2

 - Thermocouple type 

T

 

ofs 

Sensor  Offset

  -  Offset  value  to  be  added  to  the  measured  temperature  to 

compensate sensor error. 

spl 

SP Low Limit

 - Lower range for 

SP1

 and 

SP2

.  

SPL

 must be programmed 

with a lower value than 

spK

spK 

SP High Limit

 - Upper range for 

SP1

 and 

SP2

.  

SPx

 must be greater than 

spl

kys 

OUTPUT  Hysteresis

:  defines  the  differential  range  between  the  temperature 

value at which the OUTPUT is turned on and the value at which it is turned off. 

In degrees. 

ale 

Alarm Enable

0

  Alarm disabled; 

 1

  Buzzer alarm and output 2 pulsed (1 second); 

 2

  Buzzer alarm and output 2 pulsed; 

 3

  Output 2 pulsed (1 second); 

 4

  Output 2 pulsed. 

Function available for models N322T-NTC and N322TB-NTC. 
For  N322T-NTC  model 

1

  and 

2

  parameter  work  as 

3

  and 

4

  parameters 

respectively. 
Alarm function works only for 

fot

 = 

2

 parameter.

 

Alt 

Alarm Time

 - Sets the time for which the alarm will be triggered. 

 1

 

to

 

255

 seconds 

To turn the alarm off before the programmed time, just press 

 for 1 second. 

Function available for models N322T-NTC and N322TB-NTC. 
Alarm function works only for 

fot

 = 

2

 parameter.

 

Act 

Control action for OUTPUT 1: 

0

     Reverse: For heating applications. Outputs turn on when  temperature is 

lower than SP. 

1

     Direct:  For  cooling  applications.  Output turns  on  when  temperature  is 

above SP. 

(nt 

Control

 - Associates Setpoints and Outputs.  

0

  Setpoint  is  assigned  to  OUTPUT1  and  Setpoint  to  OUTPUT2  (factory 

setting). 

1

  Setpoint  is  assigned  to  OUTPUT2  where  as  Setpoint  is  directed  to 

OUTPUT1. 

oft 

Off time

 - Defines the minimum 

off

 time for control OUTPUT. Once OUTPUT is 

turned  off,  it  remains  so  for  at  least  the  time  programmed  in 

oft

.  For 

thermocouple inputs this parameter is not available. This parameter is intended 

for refrigeration systems where  longer compressor life is desired. For heating 

systems, program 

oft

 to zero. Value in seconds, 0 to 999 s. 

Ont 

On time

 - Defines the minimum 

on

 time for control OUTPUT. Once turned on, 

OUTPUT  remains  so  for  at  least  the  time  programmed  in 

ont

.  For 

thermocouple inputs this parameter is not available. This parameter is intended 

for  refrigeration  systems  where  increased  compressor  life  is  desired.  For 

heating systems, program 

ont

 to zero. Value in seconds, 0 to 999 s. 

dly 

Delay

 - Delay time to start control. Upon power-on, control OUTPUT 1 is kept 

off

  until  the  time  programmed  in 

dly

  is  elapsed.    Its  usage  is  intended  to 

prevent  multiple  compressors  to  start  simultaneously  after  the  turn-on  of  a 

system with several controllers.  Value in seconds, 0 to 250 s. 