Novus N322S Operating Manual Download Page 1

 

TEMPERATURE CONTROLLER 

N322S 

OPERATING MANUAL - V1.9x G 

 

 

Man 5001252 

The N322S is a controller intended for solar water heating applications. It controls the water 

circulation system based on the difference of temperature between the solar collector and 

the storage tank (or swimming pool). 
The instrument contains two  NTC-type temperature sensors  and  two  outputs:  a  control 

output (

output 1

) for activating the water circulation pump and a booster output or support 

output (

output 2

). It provides protections  against overheating and freezing  to the piping, 

preventing damages to the system. 

SPECIFICATIONS 

INPUT SENSOR:

 

 

Thermistor NTC, 10 k

 

@ 25 °C; Range: –50 to 120 °C (–58 to 248 °F); Accuracy: 0.6 °C 

(1.1 °F); 

Maximum error in the interchangeability of original NTC sensors: 0.75 °C (33.35 °F). This 

error can be eliminated through the 

offset

 parameter of the equipment. 

Note:

 For the NTC thermistor option, the sensor comes with the equipment. Its operating 

range is limited to –30 to +105 °C (–222 to +221 °F). It has cable of 3 m in length, 2 x 0.5 

mm², and can be extended up to 200 meters. 

Measurement Resolution:

.............................................................. 0.1 º from –19.9 to 119.9 º 

 ..................................................................................... 1 ºC elsewhere 

Note

:  The  equipment keeps its precision all over the range, despite the lack of display 

resolution in a part of the range does not allow its visualization.  

Circulation Output (OUTPUT1):

 ........................................................................... Relay SPDT 

 ....................................................................... 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive) 

Support Output (OUTPUT2):

 ........................................................ Relay: 3A / 250 Vac, SPST 

POWER SUPPLY: 

 .......................................... 100 to 240 Vac/dc  

±

 10 % 

 

Optionally:  .......................................... 12 to 30 Vdc/ac 

 

Mains Frequency:  ........................................ 50~60 Hz 

 

Power Consumption: ............................................ 5 VA 

DIMENSIONS

Width x Height x Depth: ............................................ 75 x 34 x 75 mm 

 

Weight:  .......................................................................................100 g 

 

Panel: ................................................................................ 70 x 29 mm 

ENVIRONMENT: 

Operating: ............................................. 0 to 40 °C (32 to 104 ºF) 

 

Storage temperature: ......................... -20 a 60 °C (-4 to 140 ºF) 

 

Relative humidity: ............................ 20 to 85 % non-condensing 

CASE:

  .................................. Polycarbonate UL94-2; Protection: Front panel: IP65, Box: IP42  

 .................................................................................................... Suitable wiring: Up to 4.0 mm

2

 

RS-485 digital communication; RTU MODBUS protocol (Optional) 

 Serial interface not isolated from input circuitry. 

Serial interface isolated from power supply input, except in 24 V models. 

INSTALLATION 

It is important to follow the recommendations below: 

  Signal wires should be installed in grounded conduits and away from power or contactor 

wires. 

  The instrument should have its own power supply wires that should not be shared with 

electrical motors, coils, contactors, etc. 

  Installing RC filters (47 R and 100 nF, series combination) is strongly recommended at 

contactor coils or any other inductor. 

  Use protection devices like circuit breakers and fuses. 

ELECTRICAL WIRING 

Fig. 1

 below shows the controller connections to sensor, mains and outputs. 

 

Fig. 1

 – N322S terminals 

OUTPUT1 is the Circulation Output. 
OUTPUT2 is the Support Output. 
* The serial communication interface is optional. 

OPERATION 

The N322S contains several parameters that need to be configured in order to determine 

system behavior. 
These configuration parameters are organized in groups, the so called 

parameter

 

levels

Level 

Function 

Temperature Measurement 

Setpoint Adjustment 

Configuration 

Calibration 

Upon power-up, the N322S display shows for 1 second its firmware version. This information 

is useful when consulting the factory. 
Then, the temperatures of the sensors are displayed, according to the scheme defined in the 

parameter “

ind

”.

 

This is the parameter level 

0

 (temperature measurement level). 

For accessing the level 1, press the 

  key  for 2 seconds until the  “

D0n

”  parameter 

appears. Release the 

 key to remain on this level Pressing the 

 key successively the 

other parameters in this level are displayed. 
For accessing the level 2, press the 

  key  for 4 seconds until the  “

unt

”  parameter 

appears. Release the 

 key to remain on this level. Press 

 again to access the other 

parameters of this level. After reaching the last parameter, the controller will return to the 

temperature measurement level. 
Use the 

 and 

 keys to alter a parameter value. The display alternates the parameters 

prompts and their respective value. 

Notes

1  The configuration will be saved by the controller upon advancing to the next 

parameter in a level. 

2

 

If no keypad activity is detected within 20 seconds, the controller saves the 

current parameter value and returns to the measurement level. 

 
 
 
 

Level 1 – 

Setpoint

 Adjustment 

At this level, the display presents  the setpoint parameters. They define the differential 
temperatures  values  for  the  control. Use the 

  and 

 

keys for setting  the  suitable 

values. 

D0n 

 

Differential setpoint for 

activating

 the pump. 

When the difference between T1 and T2 is 

higher

  than the value 

configured in 

d0n

 the pump will be turned on. 

Max 

d0f

 value:  20 ºC. 

D0f 

 

Differential setpoint for deactivating the pump. 
When the difference between T1 and T2 is lower than the value configured in 

d0f

 the pump will be turned off. 

Adjustable between 1 ºC and 

D0n

Sp1 

Setpoint for activating booster output. 
Adjustable between 

Spl

 and 

SPk

Level 2 – Programming Level 

This level contains other configuration parameters that are needed for establishing a proper 

system performance. 

Unt 

Unit

 

Temperature Unit

 – Defines the temperature unit to be displayed. 

0

  Temperature in degrees Celsius 

1

  Temperature in degrees Fahrenheit 

ind 

Indication

 

Temperature value exhibited on the display. 

Temperature of the collectors (T1) 

Temperature of the storage tank (T2)

 

2

  Temperature difference between the sensors (T1 –T2) 

3

  Alternates the indication of (T1), (T2) and (T1-T2) at every 3s. 

I(e 

   Ice 

Setpoint for low temperature. 
When the temperature in the solar collector is lower than the value here 

configured, the pump is turned on, preventing the water from freezing in the 

pipe system and causing damages to it. 
Adjustable between 

spl

 

and 

spk

kti 

High 

Temperature 1

 

Setpoint for high temperature (at collector). 
When the temperature in the collector is above the value here configured, 

the pump is turned off, avoiding the overheated water from damaging the 

pipe system. 
Adjustable between 

Spl

 and 

SPk

Kt2 

High 

Temperature 2 

Setpoint for high temperature at S2 (storage tank). 
When the temperature at the sensor S2 is above the value here configured, 

the pump is turned off in order to avoid thermal discomfort.  
This function is useful in swimming pool heating systems which do not use 

dedicated third sensor. 
Adjustable between 

spl

 and 

spk

A(1 

Action 1 

Action type for booster output (

SP1

): 

0

  Reverse  Action Control. Good for heating. Turns on the booster 

output when temperature is below SP1. 

1

  Direct Action Control. Good for cooling. Turns on the booster output 

when temperature is higher than SP1. 

kys 

Histeresis 

Antifreezing temperature hysteresis of sensor S1 (

i(e

). In degrees. 

Adjustable between 0.1 and 50.0 ºC 

Ky1 

Histeresis 1

 

Overheating temperature hysteresis of sensor S1 (

kt1

). In degrees. 

Adjustable between 0.1 and 50.0 ºC 

Ky2 

Histeresis 2

 

Overheating temperature hysteresis of sensor S2 (

kt2

). In degrees. 

Adjustable between 0.1 and 50.0 °C. 