06/16 Rev. 04
SERVICE MANUAL
Service Electronics Gen. 3
64-xx Gen. 3 – DPM Gen. 3 – PEM – ALX 92x Gen. 3 – ALX 73x (PMA)
27
5
PAUSE\
(Input)
A high-low-transition switches the printer into the USI-paused mode.
A further high-low-transition switches the printer back into the online mode.
If parameter
DP INTERFACE > Start print mode
is set to
Level high active
or
Level
low active
, any activating of the PAUSE\ signal stops the printing after the
current label.
Features:
• „USI Pause“ is displayed
• ERROR\ is activ (low)
• If a print job is available: DATA RDY\ is inactive (high)
• Start print signals are suppressed
• Reprint requests are proceeded after switching into online mode.
• Precondition: START PRINT\ inactive (high).
6
REPRINT\
(Input)
The last printed label is being reprinted as long as REPRINT\ is low.
Minimum reprint quantity: 1 label.
Preconditions:
• The label which is ought to be reprinted, must be ready printed and dis-
pensed.
• Printer is in online mode.
• If a REPRINT\ is triggered while the printer is in USI-pause mode, the
reprint will be proceeded as soon as the printer is switched back in on-
line mode.
• Precondition: START PRINT\ inactive (high).
7
24V_EXT
(Voltage supply)
Voltage supply for external sensors
8
GND_EXT
(GND)
Ground contact
Pin Signal
Function
[Tab. 6]
(Cont.)Signal designations and functions of the USI interface.
Summary of Contents for ALX 92x
Page 3: ...Release 3 6 2016 SERVICE MANUAL ALX 92x Print Apply system ...
Page 356: ...12 14 Rev 05 SERVICE MANUAL Service Electronics 64 xx Gen 2 DPM Gen 2 ALX 92x Gen 2 43 ...
Page 508: ...Edition 1 3 2016 INSTALLATION MANUAL AI retrofitting kit for ALX 92x ...
Page 509: ......
Page 511: ...Installation Manual AI retrofitting kit for ALX 92x 03 2016 4 Content ...
Page 520: ...Installation Manual AI retrofitting kit for ALX 92x 03 2016 00 13 Installation ...
Page 521: ......
Page 522: ...Novexx Solutions GmbH Ohmstraße 3 85386 Eching Germany 49 8165 925 0 www novexx com ...