~ 27 ~ 

NOVATEK-ELECTRO   

                                                                                               

UBZ-304

 

The procedure for changing the settings on the advanced user level is the same as user-level (it.5.2.5), but the 

parameter recording does not depend on the inscription "ADV" presence in the fourth line of the indicator.  

If the parameter is not in the list of MNS (the fourth line of the indicator has the inscription "OFF MMSP"), then to 

change the value of the parameter it is necessary preliminary to include it in the list of MNS.  

 

At the advanced user level the availability of any parameter at the user level can be disabled or enabled.  
To do this it is required the following: 

  using 

DOWN

 and 

UP

 buttons, select the parameter (Fig.5.9); 

  enter the menu where setting is changed by pressing 

SETUP

 button;  

  press both buttons 

SETUP

 and 

DOWN

In  case  of  restricting  access  to  change  the  parameter  at  the  user  level  in  the  fourth  line  of  the  indicator  the 

inscription “ADV” will display

 

 

5.2.7 Factory settings 

Factory settings are possible in two ways. 

The first method: set the parameter “Default Factor” to “On”; after exiting from the mode for setting the factory 

settings will be restored. 

This method does not recover the following settings:  

 

access code of advanced user ("Password"); 

 

current time and date; 

 

clock correction ("Correct Time"); 

 

the unit operating time ("Time UBZ"); 

 

operating time of the motor ("Time motor"). 

The  second  method:  when  UBZ  energizing,  hold  pressed  for  two  seconds  the  buttons 

SETUP

  and 

RES/MEM/SEL

. Factory settings are restored (advanced user password - 123). 

This method does not recover the following settings:  

 

the unit operating time ("Time UBZ"); 

 

operating time of the motor ("Time motor"). 

 

clock correction ("Correct Time"). 

After you complete the installation of factory parameters, UBZ will start operation in the mode of MNS, the list of 

which the settings are included: 

 

motor rated current

, “Rated Inom”.

 

 

current time setting

, “

Real Time

”;

 

 

CT current

, “CT nom 

i

”;

 

 

5.2.8 Real time setting 

To set the real time it is necessary the following: 

1) pressing 

SETUP

 button, enter the parameters setting mode; 

2) using 

UP

 and 

DOWN

 buttons, select parameter 

Real Time

3) press the button 

SETUP

 (Fig.5.10); 

 

 

 

Figure 5.10

 

 View of the display when setting the time  

 

4) using 

UP

 and 

DOWN

 buttons, select the desired date and press the button 

RES/MEM/SEL

 ; 

5) repeat it. 4 to set the month, year, hour and minute.  

When recording minutes (at the moment of pressing the button 

RES/MEM/SEL

), the number of seconds will be 

automatically set to zero. 

If you move to the next parameter without changes, instead of the button 

RES/MEM/SEL

, press the button 

SETUP

If no button is pressed for 15 seconds, UBZ will automatically switch to the parameter view mode. 

 

5.2.9 UBZ faults reset on front panel 

Fault reset is performed when the motor is off. To reset the faults on the front panel, press simultaneously the 

buttons 

SETUP

 and 

DOWN

, in this case: 

 

 faults are reset regardless of whether ARS is disabled or enabled (besides the current faults and faults by the 

presence of motor currents when load relay is off); 

 counting of ARS is off; 

 in the absence of the current troubles the motor is off.  

 

5.2.10 Energy meters reset 

Summary of Contents for UBZ-304

Page 1: ...TRO LTD thanks you for purchasing our products You will be able to use properly the product after carefully studying the Operating Manual Keep the Operating Manual throughout the service life of the p...

Page 2: ...onnection 21 5 1 2 Selection of Current Transformers CT 21 5 1 3 General 21 5 1 4 Unit Installation 22 5 1 5 UBZ 304 connect 23 5 2 UBZ Control 24 5 2 1 Modes of UBZ control and status 24 5 2 2 Measur...

Page 3: ...dure 37 7 TRANSPORTATION AND STORAGE 38 8 SERVICE LIFE SHELF LIFE AND MANUFACTURER WARRANTY 38 9 ACCEPTANCE CERTIFICATE 38 10 CLAIMS DATA Appendix 39 CURRENT PROTECTION WITH DEPENDENT TIME DELAY Appen...

Page 4: ...OUNTING WORKS AND MAINTENANCE WITHOUT DISCONNECTING THE PRODUCT FROM THE MAINS TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED...

Page 5: ...gn version UBZ provides continuous monitoring of mains voltage parameters current values of the phase line currents of three phase electrical equipment for 415V 50Hz and checking the resistance values...

Page 6: ...ltages and currents calibration factors is added Version 9 control algorithms by the engine on analog inputs are added 1 3 CONTROLS AND OVERALL DIMENSIONS Overall dimensions of UBZ are given in Fig 1...

Page 7: ...n the parameters setting mode 11 Button DOWN is scrolling of displayed parameters in the parameter view mode and scrolling of the menu in the parameters setting mode 12 Button RES MEM SEL is the param...

Page 8: ...oad VA not more 5 0 Weight not more kg 0 34 Overall dimensions Fig 1 1 H B L mm 110 96 88 3 Position in space free Housing material self extinguishing plastic Table 3 3 Characteristics of built in rel...

Page 9: ...ll drop lower than 1 2 In Maximum phase current achieved during this period is the maximum starting current 3 I t 3 I t 0 1 600 2 10 Start i Overload i Start time 42 43 44 Voltage Effective values of...

Page 10: ...d with MW MVA MVAr 5 If the temperature value exceeds specified limits then the indicator displays the alarm code in accordance with table 5 13 If the temperature sensor is disabled by software then t...

Page 11: ...sable 2 On AR protection is on ARS is enabled 161 Negative sequence current protection Actuation setting I2 rev tresh 5 20 10 It is set as percentage of rated current 162 Tripping delay s I2 rev delay...

Page 12: ...otec 0 2 2 0 Off protection is off 1 OnnAR protection is on ARS after tripping is disable 2 On AR protection is on ARS is enabled 179 Maximum line voltage V Umax tresh 330 450 415 180 Tripping delay f...

Page 13: ...t 0 2 0 0 Off protection is off 1 OnnAR protection is on ARS after tripping is disable 2 On AR protection is on ARS is enabled 194 Motor control and ARS ARS time after protection operation at minimum...

Page 14: ...abled 1 Pt100 of Pt100 type 2 Ni100 of Ni100 type 3 Ni120 of Ni120 type 204 Motor trip temperature Temp S2 Off M 0 220 180 205 Warning temperature Temp S2 Alarm 0 220 170 206 Temperature correction of...

Page 15: ...tional relay is enabled Timer value s Relay F time 0 300 30 See it 2 it 3 of the parameter Relay F mode address 214 215 Star delta mode Switching time s Delay RP RF 0 1 2 0 4 The time between the load...

Page 16: ...Version 9 The parameter value depends on software version 230 Indicator illumination1 Indicator L 0 2 1 0 Off illumination is off 1 On15s illumination is on for 15 s after pressing any buttons 2 On i...

Page 17: ...current factor to negative sequence voltage factor for thermal overload undercurrent protection in phases delayed starting rotor blocking overheating of windings for minimum line voltage for maximum...

Page 18: ...are assumed ARS after tripping will not occur regardless of the value of I2 rev protec parameter The coefficient of negative voltage current sequence is characteristic of unbalance of three phase vol...

Page 19: ...n you should enter the response time in case of double overload T2 the parameter of Thermal delay Current time characteristic with different values of T2 is given in Fig 3 4 For the standard recommend...

Page 20: ...751 and DIN 43760 3 4 9 Voltage protection In UBZ voltage protection before enabling the load it is necessary to check the corresponding set points and depending on their value the load relay enabling...

Page 21: ...upplier or manufacturer Carefully study the Operating Manual pay special attention to the connection diagram to power the product If you have any questions regarding the installation of the product pl...

Page 22: ...5 91 5 mm 0 5mm tolerance the distance between UBZ panels top bottom and side and the relevant surfaces of the panel should be at least 10 mm if it is assumed to have operational use of communication...

Page 23: ...insulation 23 to one of output contacts of MS If the motor housing is not grounded or network with isolated neutral is used or neutral wire is not connected to UBZ terminal it is necessary to connect...

Page 24: ...0 are closed when relay is off the contacts 16 17 and 20 21 are closed 5 2 UBZ CONTROL 5 2 1 Modes of UBZ control and status UBZ has five control modes Keyboard blocking MNS User level Advanced user l...

Page 25: ...g the keyboard no button is pressed within 15 s and setting of blocking has not been disabled by the user the keyboard is blocked again 5 2 4 Mode of Minimum number of settings MNS Mode of MNS is desi...

Page 26: ...play instead of the inscription OFF MMSP the inscription MMSP should remain The value of the parameter in the user mode can be changed if the fourth line of the indicator has only the inscription MMSP...

Page 27: ...s are restored advanced user password 123 This method does not recover the following settings the unit operating time Time UBZ operating time of the motor Time motor clock correction Correct Time Afte...

Page 28: ...simultaneously press UP and DOWN buttons 2 when Start Power St AR the load relay will be enabled after ARS time 3 when Start Power St 2s the load relay will be enabled within 2 seconds after energizin...

Page 29: ...er 0 1 2 3 4 5 6 7 ASCII code 30 Hex 31 Hex 32 Hex 33 Hex 34 Hex 35 Hex 36 Hex 37 Hex Character 8 9 A B C D E F ASCII code 38 Hex 39 Hex 41 Hex 42 Hex 43 Hex 44 Hex 45 Hex 46 Hex In RTU mode 8 bit dat...

Page 30: ...t changed but the format of the transmission data and control of data is based on the Table 5 4 Table 5 4 Data packet in ASCII mode Name Description STX Start character 3A Hex ADR1 UBZ communication a...

Page 31: ...operation day Time UBZ 217 Motor operating time day Time motor 218 Access code of user Users code 219 Access code of advanced user Password 220 Restoration of factory settings Default Factor 221 The u...

Page 32: ...mitting device In case of mismatching the generated and received Cyclic Redundant Check the error message will be generated The field of Cyclic Redundant Check has two bytes CRC in the message is tran...

Page 33: ...l relay operation 00 alarm relay 01 time relay 10 star delta Bit 6 0 MNS mode is disabled 1 MNS mode is enabled Bit 7 0 clock battery is normal 1 the clock battery should be replaced Bit 8 0 normal op...

Page 34: ...and The master should repeat the message later when the slave is freed 07h NEGATIVE ACKNOWLEDGE UBZ cannot perform the program function received in request 5 4 9 Remote control of the motor using RS 2...

Page 35: ...the command UBZ RESTART the delay of at least 100 ms should be provided ATTENTION WHEN THE MOTOR IS ENABLED THE FULFILLMENT OF COMMAND UBZ RESTART RESTART IS DISABLED 5 4 12 UBZ factory settings using...

Page 36: ...alance 314 14 901 14 Minimum insulation resistance of motor winding Insul Res Insulation resistance 315 15 901 15 Mains minimum frequency F min Frequency 316 16 902 0 Mains maximum frequency F max Fre...

Page 37: ...fault code Stop nAR The restart of the motor is possible only after de energizing and re energizing of UBZ unit St motor start and shutdown is permitted the load relay is disabled with issuance of co...