MODELS

NFX-WS-** = Sounder Non Isolation

NFXI-WS-** = Sounder Isolation
NFX-WSF-** = Sounder Strobe Non Isolation

NFXI-WSF-** = Sounder Strobe Isolation
NFX-WF-** = Strobe Non Isolation

NFXI-WF-** = Strobe Isolation

** = Denotes colour

GENERAL

The range of intelligent AV devices are designed to be connected to analogue addressable fire 

alarm systems.

These devices must only be connected to control panels that use a compatible proprietary 

analogue addressable communication protocol.

These devices receive their power from the loop, and can be controlled via the communication 

protocol(s).

The sounders have three volume levels and 32 tone sets. Models (NFXI-WS-**, NFXI-WSF-**, 

NFXI-WF-**) containing the character ‘I’ prior to the Customer ID code include in built isolation 

providing short circuit protection of the loop.

Up to 159 addresses are available. (consult the panel instructions to confirm compatibility)

These are selected via the two rotary switches. The ‘tens’ digits go from 0 to 15 and the ‘units’ 

from 0 to 9. 

Note: if the control equipment is not capable of taking more than 99 module addresses, a fault 

condition will be generated for every address over 99.

SPECIFICATIONS 

Operating temperature range -25 to +70

o

C

Relative humidity up to 93% (± 3%) - non condensing

Terminal Size 2.5mm

2

 - maximum

For isolator specification refer to document SP04-2289 available on request

INSTALLATION INSTRUCTIONS FOR WALL MOUNTED LOOP POWERED AD-

DRESSABLE SOUNDERS, SOUNDER STROBES AND STROBE ONLY

NFX-WS-**  

NFXI-WS-**

NFX-WSF-**  

NFXI-WSF-**

NFX-WF-**  

NFXI-WF-**

Signaling Line Supply Voltage (non isolation)

15 to 32VDC (24VDC typical)

Signaling Line Supply Voltage (isolation) 

15 to 29VDC (24VDC typical)

Max current consumption (non isolation) (High Volume 

Tone 8 @24V)

 5.58mA

 8.86mA

N/A

Max current consumption (isolation) (High Volume Tone 

8 @24V)

 5.77mA

 9.05mA

N/A

Sound Output to EN54-3 (High Volume Tone 8 @24V)

95dB(A) ± 3dB

N/A

Beacon flash rate

N/A

1Hz

1Hz

Max current consumption (non isolation) NFX*-WF-**

N/A

 N/A

 3.28mA

Max current consumption (isolation) NFX*-WF-**

N/A

 N/A

 3.47mA

Quiescent Current

450uA

TERMINAL  

CONNECTIONS

VOLUME SETTINGS

Volume setting is selected by SW6 

and SW7 of the 8 way DIP switch. The 

appropriate tone set is selected by SW1 to 

SW5 of the 8 way DIP switch (see table 1). 

The 2nd stage tone (related to the 1st stage 

tone) is controlled by the fire panel via the 

protocol.

BASES/IP RATING

     

B501AP Base(IP 21C)

  

        Deep Base(IP 44)

 Waterproof Base(IP 65)

INSTALLATION

Affix B501AP base to a suitably flat wall. 

Terminate the cable to the appropriate 

terminals.  For surface mount wiring the cable 

can enter the B501AP base via the break 

outs provided.  Select 

the appropriate Tone and 

Volume settings via the 

DIP switch. 

Locate the main 

assembly on to the base 

by rotating until it locks 

into place.

CONTINUITY 

SPRING

The B501AP base 

incorporates a 

continuity spring 

between terminals 

2 and 4. This allows the continuity of the field 

wiring to be checked without the need for the 

device to be present. Inserting the device will 

disengage the spring. Removing the device 

will close the loop.  

ANTI TAMPER LOCK

The B501AP base 

also includes a tamper 

resistant feature 

that when activated 

prevents removal of 

the unit without the 

use of a special tool.

This method is 

consistent with the 

anti tamper feature 

across all devices 

using this base.  This 

prevents the device 

being turned to 

enable its release.

SW6 SW7 Volume Setting

OFF OFF HIGH
OFF ON

MEDIUM

ON

OFF LOW

ON

ON

LOW

Breakout

If the waterproof option is required then the 

wall gasket must be fitted behind the deep 

base, and the sealing o-ring fitted after at-

taching the low profile base.

1

2

3

4

+

_

+_