Walk Test
Alter Status
NFS-3030 Programming Manual P/N 51345:C 11/4/03
67
Soft Keys
BASIC/ADVANCED:
Press to toggle between the two choices. Stop at the desired test.
SILENT/AUDIBLE:
This soft key is for future use. Walk test is audible.
PARAMETER:
Press to scroll through the choices. Stop at the desired parameter. Choosing the
loops parameter will bring up the Walk Test loops programming screen (Refer to Figure 4.10 )
Choosing the panel parameter will bring up the panel Walk Test screen (Refer to Figure 4.11)
DISABLE ACS BOARDS:
This soft key allows the operator to disable ACS devices during Walk
Test. Press to toggle between the two choices,
YES
(disable) and
NO
(enable). Default:
YES
Figure 4.10 Walk Test Loops Programming Screen
This screen appears when
LOOPS
is chosen as a parameter at the Walk Test Menu. The chosen
settings are displayed (
BASIC,
AUDIBLE
in Figure 4.10), and installed loops will display with a
participation field. The up and down arrow keys on the keypad navigate through the fields. Choose
YES
for participation,
NO
for no participation, using the
NEXT SELECTION
(+)/
PREVIOUS SELECTION
(-) keys on the keypad.
Soft Key
START TEST:
Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes
ABORT
, and can be pressed at any time to exit Walk Test.
NEXT
TEST:
This key appears for Advanced Walk Tests when the panel parameter is chosen at the
Walk Test Menu Screen. Refer to Figure 4.11 for the location of this key. Press it to progress from
one activation to the next, latching the new point and releasing the latch on the previous point.
If this parameter
is chosen...
The participating devices/points in Basic
Test will be...
The participating devices/points in
Advanced Test will be...
LOOPS
All devices/points on all the FACP SLCs
that are set to participate in Walk Test with
the exception of logic equations, whose
activation is suspended.
All devices/points on all the FACP
SLCs, as well as panel circuit outputs
that are set to participate in Walk Test.
PANEL
The entire panel - all devices/points set to
participate in Walk Test - will participate with
the exception of logic equations, whose
activation is suspended.
The entire panel - all devices/points set
to participate in Walk Test including
panel circuit outputs - will participate.
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I J U L 1 9 , 2 0 0 2
W A L K T E S T
S E T T I N G S : B A S I C , A U D I B L E , L O O P S
L 1 : N O
L 2 : N O
L 3 : Y E S
L 4 : N O
L 5 : N O
L 6 : Y E S
L 7 : N O
L 8 : N O
L 9 : Y E S
L 1 0 : N O
S T A R T T E S T
B A C K
Once the
START TEST
soft key has
been pressed and the test begun, this
message changes to
ABORT
www.PDF-Zoo.com
Summary of Contents for NFS-3030/E
Page 60: ...Program Autoprogram Menu 60 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 128: ...Type Codes FlashScan Codes 128 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 134: ...Glossary Glossary 134 NFS 3030 Programming Manual P N 51345 C 11 4 03 www PDF Zoo com...
Page 142: ...NFS 3030 Programming Manual P N 51345 C 11 4 03 142 INDEX www PDF Zoo com...