GENERAL

The System Sensor FSB-200 and FSB-200S are intelli-
gent, addressable projected beam smoke detectors for pro-
tecting open areas with high and sloping ceilings, and wide-
open areas, where spot-type smoke detectors are difficult
to install and maintain. Ideal applications are atriums, ca-
thedral ceilings, aircraft hangers, warehouses, sporting are-
nas, concert halls, and enclosed parking facilities. They
are compatible with the NFS-3030 and NFS-640 in
FlashScan® or CLIP mode, as well as legacy products like
the AM2020, AFP1010, AFP-400, AFP-300, AFP-200, and
AFP-100 (CLIP mode). Installation of the single-ended re-
flective design is much quicker than a dual-ended projected
beam detector. Alignment is easily accomplished with an
optical sight and a two-digit signal strength meter incorpo-
rated into the beam detector. Listed for operation from –
22°F to 131°F, the FSB-200 and FSB-200S are usable in
open area applications where temperature extremes ex-
ceed the design limits of other types of smoke detection.

The FSB-200 and FSB-200S are a transmitter/receiver unit
and a reflector. When smoke enters the area between the
unit and the reflector it causes a reduction in the signal
strength. When the smoke level (signal strength) reaches
the predetermined threshold, an alarm is activated. The
detectors have four standard sensitivity selections as well
as two Acclimate Plus™ settings. When either Acclimate
Plus™ setting is selected, the detector’s advanced soft-
ware algorithms automatically adjust to the optimum sen-
sitivity for the specific environment. The protection range
is 16 to 328 feet and there are built-in isolators for Style 7
operation.

The FSB-200S has an integral sensitivity test feature of a fil-
ter attached to a servomotor inside the detector optics. Acti-
vation of the RTS451 remote test station moves the filter into
the pathway of the light beam, testing the detector’s sensitiv-
ity. This sensitivity test feature allows the user to quickly and
easily meet the annual maintenance and test requirements of
NFPA 72, without physical access to the detector. The servo-
motor must be powered by +24 VDC, not SLC power.

FEATURES

• Transmitter/receiver built into same unit.
• Six user-selectable sensitivity levels.
• 16' to 328' (use BEAMLRK beyond 230') protection range.
• Removable plug-in terminal blocks.
• Digital display — no special tools required.
• Built-in automatic gain control compensates for signal

deterioration from dust buildup.

• Optional remote test station.

Section:  Intelligent/Addressable Devices

DN-6985 •  H-212

This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact NOTIFIER.Phone: (203) 484-7161  FAX: (203) 484-7118

12 Clintonville Road, Northford, Connecticut 06472

NOTIFIER® is a Honeywell company.

FSB-200(A)

 and 

FSB-200S(A)

Single-Ended, Reflected-Type

Addressable Beam Smoke Detectors

April 14, 2005

FSB-200
with
Reflective
Plate

FSB-200 with
BEAMMMK

• Optional long-range kit (BEAMLRK) for applications in

excess of 230' (70 m).

• Optional multi-mount kit (BEAMMMK) providing ceiling

or wall mount capability with increased angular adjust-
ment.

• Optional heater kits (BEAMHK and BEAMHKR) for pre-

vention of condensation (not intended to increase or re-
duce the specified operating temperature).

Acclimate Plus™ is a trademark of NOTIFIER.

S2522

(FSB-200,

FSB-200S)

California

State Fire

Marshal

7260-0028:228

MEA

95-04-E

Permit # 2167

MARYLAND

State Fire Marshal

S911 Vol. 109/
CS308 Vol. 35

(FSB-200A,

FSB-200SA)