background image

1                                                                               I56-5917-000 

INSTALLATION AND MAINTENANCE INSTRUCTIONS  

 
Model FS-BSO   

Addressable Base Sounder 

Notifier by Honeywell

9 Columbia Way Baulkham Hills,NSW 2153 

Australia

www.notifier.com.au

SPECIFICATION 

Item 

Parameter Description 

Note 

Operating Voltage 

24VDC( 15 to 32VDC) 

 

Avg. Standby Current 

<400µA 

24VDC, No Communication, No sounding 

Alarm  Current 

<6mA High 

Volume, 

24VDC 

<4mA 

Low Volume, 24VDC 

Operating Temp 

-10

 to +55

 

 

Humidity 

10 to 95% R.H.  

Non-condensing 

Ingress Protection 

IP21C 

 

Approved Sound Pressure 

Level 

83±4dB(A)    

1m , High Volume, Tone 21 @24V(2.7mA)         *Approved to EN54-3 

High Volume . 

Most Favorable  Sound 
Pressure Position 

92±3dB(A)    

1m , 90°,High Volume, Tone 21 @24V(2.7mA)  **     

94±4dB(A)    

1m , 90°,High Volume, Tone 13 @24V(3.0mA)  ** 

95±3dB(A)    

1m , 90°,High Volume, Tone 12 @24V(2.5mA)  ** 

94±7dB(A)    

1m , 90°,High Volume, Tone 19 @24V(2.5mA)  ** 

Low Volume .  
Most Favorable  Sound   

Pressure Position 

88±3dB(A)    

1m , 90°, Low  Volume, Tone 21 @24V(2.0mA) ** 

88±3dB(A)    

1m , 90°,Low  Volume, Tone 13 @24V(2.0mA)  ** 

85±4dB(A)    

1m , 90°,Low  Volume, Tone 12 @24V(1.7mA)  ** 

85±5dB(A)    

1m , 90°,Low  Volume, Tone 19 @24V(1.8mA)  ** 

Tone Type 

See table 1:  ‘Sound setting  ’ for detailed tones 

Height 52mm 

 

Diameter 122mm 

 

Weight 196±6g 

 

Note:  *  Detailed description see table A                                                                                  
         **These volume & tone settings are not approved to EN54-3.  
Meet the following Standards requirements

EN54-3 

AS ISO 7240.3:2014          

 

 

Before installing and using the product, please read the system wiring 
and installation manual thoroughly. If the products will be installed in an 
existing operational system, inform

 

the operator and local authority that 

the system will be temporarily out of service, disconnect

 

power to the 

control panel before installing the products. 
NOTICE: This manual should be left with the owner/user of this 
equipment. 

GENERAL 

FS-BSO is an intelligent addressable AV base designed to alarm sound for 
emergency events, and be able to communicate with control panel by 
intelligent protocol. 
It is designed specifically for analogue addressable fire alarm system 
and only can be connected to control panels with a compatible 
proprietary analogue addressable communication protocol. It is 
powered from the loop and can be controlled via the communication 
protocol(s). The Base version is compatible with 200 series of 
detectors and B501 mounting base. Up to 159 addresses are available 
via two rotary selector switches.  The sounders have 2 volume levels 
(high/low) and 4 tone sets. The alarm sound can be tested on field.  

INSTALLATION 

It must be installed and wired with B501 mounting base. 
1.

 

Verify the product type matches with product drawing. 

2.

 

Set the address via two rotary selector switches. Please refer to 
“Address setting”. 

3.

 

Volume and tone setting are realized by 4 digit DIP switch. On field 
testing can be tested via DIP switch. 

4.

 

Plug the Sounder base into B501 mounting base. 

5.

 

Turn the Sounder base clockwise until it drops into place. 

6.

 

Continue turning the Sounder base clockwise to lock it in place. 

7.

 

Please refer to Detector Installation Instruction if 200 series 
detector is needed. 

SETTING 

Address setting 
Rotary-decade switches are provided for setting the base’s address 
whose range is from 1 to 159. (Default address is 01). 
Address is set by turning the switches. 
Address is calculated as below formula: Address = TENS *10 + 
ONES*1.  For instance: Address 05 = 0*10 + 5*1. 
Tamper-resistant capability  
Addressable Base sounder include a tamper-resistant capability that 
prevents its removal from the B501 base and the removal of installed 
detector without the use of a tool. 

When B501 mounting base enables tamper-resistant function, special 
tools must be used to disassemble addressable base. Please refer to 
below figure: use straight screwdriver to break specific position, then 
insert the screwdriver and maintain in its position. Then you can 
disassemble the Sounder base by turning anticlockwise 

 

Figure 1  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2

 

 

 

 

 

 

 
 

 

I5

6

-59
17-
000

 

A5665‐001

Base 
Sounder

B501 
Mounting 

200 Series 
Detector

A5665‐002 

ONES

DIP switch for 
tone setting

COMM+

COMM- 

TENS

RA Remote  
Annunciator 

Reviews: