B610LP PLUG-IN DETECTOR BASE
INSTALLATION INSTRUCTIONS
FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:
CP-651, SD-651
IN EUROPE: CP-651E, SD-651E
Before installing detectors, please thoroughly read manual I56-407,
Guide for Proper Use of System Smoke Detectors
,
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of
this manual are available from Notifier or a Notifier distributor.
NOTICE:
This manual should be left with the owner/user of this equipment.
IMPORTANT:
The detector used with this base must be tested and maintained regularly following NFPA 72 requirements.
The detector used with this base should be cleaned at least once a year.
GENERAL DESCRIPTION
The Model B610LP detector base is designed for use with Notifier model SD-651 and SD-651E photoelectronic detector
heads and CP-651 and CP-651E ionization detector heads. This two-wire base is equipped with screw terminals for the
connection of power, ground, and an optional remote annunciator.
SPECIFICATIONS
Base Diameter:
6.1 inches (155 mm)
Base Height:
0.95 inches (24 mm)
Weight:
0.3 lb. (137 g)
Mounting:
4-inch square box with or without plaster ring. Min. depth–1.5 inches
3-1/2-inch octagon box.Min. depth–1.5 inches
Operating Temperature Range:
0° to 49°C (32° to 120°F)
Operating Humidity Range:
10% to 93% Relative Humidity, Noncondensing
ELECTRICAL RATINGS -
includes base and detector
System Voltage:
12/24 VDC
Maximum Ripple Voltage:
4 Volts peak-to-peak
Start-up Capacitance:
0.02 µF Maximum
Standby Ratings:
8.5 VDC Minimum
35 VDC Maximum
120 µA Maximum
Alarm Ratings:
4.2 VDC Minimum at 10 mA
6.6 VDC Maximum at 100 mA
(Alarm current must be limited to 100 mA by the control panel.
If it is used, the RA400Z Remote Annunciator operates within the
specified detector alarm currents.)
Reset Voltage:
2.5 VDC Minimum
Reset Time:
0.3 Seconds Minimum
Start-up Time:
34.0 Seconds Maximum
N550-01-00 1 I56-646-02R
Notifier, 12 Clintonville Rd., Northfield , CT 06472-1652 (203) 484-7161
N550-01-00 4 I56-646-02R
©2001 Notifier