Notifier B610LP Installation Instructions Download Page 1

B610LP PLUG-IN DETECTOR BASE

INSTALLATION INSTRUCTIONS 

FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:   

CP-651, SD-651

IN EUROPE:  CP-651E, SD-651E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Before installing detectors, please thoroughly read manual I56-407, 

Guide for Proper Use of System Smoke Detectors

which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of 
this manual are available from Notifier or a Notifier distributor. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTICE: 

This manual should be left with the owner/user of this equipment.

IMPORTANT: 

The detector used with this base must be tested and maintained regularly following NFPA 72 requirements. 

The detector used with this base should be cleaned at least once a year.

GENERAL DESCRIPTION

The Model B610LP detector base is designed for use with Notifier model SD-651 and SD-651E photoelectronic detector 
heads and CP-651 and CP-651E ionization detector heads. This two-wire base is equipped with screw terminals for the 
connection of power, ground, and an optional remote annunciator.

SPECIFICATIONS

Base Diameter:        

 

 

 

6.1 inches (155 mm)

Base Height:          

 

 

 

0.95 inches (24 mm)

Weight:               

 

 

 

0.3 lb. (137 g)

Mounting:             

 

 

 

4-inch square box with or without plaster ring. Min. depth–1.5 inches

 

 

 

 

 

 

3-1/2-inch octagon box.Min. depth–1.5 inches

Operating Temperature Range:   

 

0° to 49°C (32° to 120°F)

Operating Humidity Range:        

 

10% to 93% Relative Humidity, Noncondensing 

               

ELECTRICAL RATINGS - 

includes base and detector

System Voltage:                

 

 

12/24 VDC

Maximum Ripple Voltage: 

 

 

4 Volts peak-to-peak

Start-up Capacitance:           

 

 

0.02 µF Maximum

Standby Ratings:               

 

 

8.5 VDC Minimum

 

 

 

 

 

 

35 VDC Maximum

 

 

 

 

 

 

120 µA Maximum

Alarm Ratings:                 

 

 

4.2 VDC Minimum at 10 mA

 

 

 

 

 

 

6.6 VDC Maximum at 100 mA

 

 

 

 

 

 

(Alarm current must be limited to 100 mA by the control panel.

 

 

 

 

 

 

If it is used, the RA400Z Remote Annunciator operates within the 

 

 

 

 

 

 

specified detector alarm currents.)

Reset Voltage:                 

 

 

2.5 VDC Minimum

Reset Time:                    

 

 

0.3 Seconds Minimum

Start-up Time:                  

 

 

34.0 Seconds Maximum

N550-01-00                                                                           1                                                                           I56-646-02R
 

 

 

 

 

Notifier, 12 Clintonville Rd., Northfield , CT 06472-1652 (203) 484-7161

N550-01-00                                                                           4                                                                          I56-646-02R

©2001 Notifier 

Please refer to insert for the Limitations of Fire Alarm Systems

www.PDF-Zoo.com

Reviews: