AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
35
Smoke Detector
Read Status
3.2 Smoke Detector
When a detector address is entered into the Point Select Screen and the ACCEPT soft key is pressed, the following screen will display if
the detector is a smoke detector.
Figure 3.2 Smoke Detector Screen - Read Status
Display
Lines 1- 4 - This could display any current event message, or, as in this example, the System Normal message.
Line 5 - This line contains the screen title and the address of the point being read.
The area between the separator lines, lines 6-14, shows all information concerning the selected point, which is N124L03D052 in the
above example.
Line 6 - Line 6 displays two statistics that display for inputs (detectors and modules) and zones; in the above example they are:
AUTOMATIC INACTIVE
The first field displays the point control. There are three designations that could appear in this field
The second field displays the point status. There are three designations that could appear in this field.
The device is a detector (an input device) so by referring to the descriptions below, it can be determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in fault or disabled, and the point is automatically controlled by the panel, the display will be one of the following:
AUTOMATIC
INACTIVE
AUTOMATIC
ACTIVE
AUTOMATIC
PREALARM
If the point is disabled, the display will be one of the following. The Fault Status field will appear if the point is in fault.
DISABLED
INACTIVE
<Fault Status>*
DISABLED
ACTIVE
<Fault Status>*
DISABLED
PREALARM
<Fault Status>*
If the point is in fault, the display will read:
Point Control
Designation
Description
AUTOMATIC
The point is being controlled automatically by the panel.
DISABLED
The point has been disabled by an outside source.
FAULT
The point is in a fault state and is no longer functioning automatically.
Table 3.2
Point Status
Designation
Description
INACTIVE
The point is currently reporting no events.
ACTIVE
The point is currently in an off-normal status.
PREALARM
The point is currently in a prealarm status.
Table 3.3
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 2 , 2 0 1 9
R E A D A D D R E S S : N 1 2 4 L 0 3 D 0 5 2
A U T O M A T I C
I N A C T I V E
E L E V A T O R L O B B Y
E A S T W I N G
F I F T H F L O O R
Z 0 0 5
S M O K E ( P H O T O )
Z 0 0 5 ,
Z 0 2 7 ,
Z 0 6 6 ,
,
,
,
,
,
,
,
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 0 : 2 2 : 3 4 A T U E J A N 2 2 , 2 0 1 9
B A C K
P E A K S : 5 6 % C O U N T : 0 2 C O : 2 0 0 P P M T E M P : 1 0 0
o
F
For FSC-851 detectors, the values appear in line
14 above. Refer to More Information on page 14
for explanation of fields.