Nortroll LineTroll 110Em User Manual Download Page 12

 

        

LINETROLL 110E

 /110Eµr User Guide February 2010              Page 12 of 16 

7.

 

TECHNICAL 
 SPECIFICATIONS 

 
Nominal voltage :     6-69 kV 

Starting criteria :                 

 

Line energised for at least 5 
seconds followed by a stepped 
instant current increase of  6, 12, 
25, 60 or 120A 

OR

  

 

absolute phase current exceeding 
250, 500, 750, 1000A 

AND  

 

a three-phase disconnection of the 
line within 5 sec. 

 
Required fault duration:  > 60ms  (20ms on 

request) 

Reset criteria:  

1)

 

Voltage/Current reset

 after 30sec. 

         (Can be disabled)

 

The minimum required current for start/reset, 
depends on the settings of di/dt or threshold

Thr.hold [A] 

Min. start/reset 

current [A] 

250 

10 

500 

50 

750 

50 

1000 

50 

 

di/dt 

[A] 

Max load 

current *) 

Min. start/reset 

current [A] 

75A 

12 

75A 

25 

300A 

16 

60 

300A 

16 

120 

1000A 

50 

*) 

Maximum load current defines the level 

for saturation where di/dt sensor cannot 
detect the programmed increase. 

NB!  If I(load) > Max load 

 It may start 

flashing without any fault! 

 
2)

  

Timer reset

 2h, 6h, 12h, or 24h.   

 

3)

  

Manually

 (KBN-4 reset tool/ magnet) 

Line diameter:  

5 – 36mm 

Current consumption:    

    Non-activated:        LT-110Eµ: 30-40µA 

LT-110Eµr: 300 µA 

Activated (flashing):  4 mA. 

Battery:            3.6 V 16,5Ah type KBB-11 

Recommended battery replacement approx. 
every 10 years (5 years for LT 110Eµr) or 
every 1500 operational hours, whichever 
comes first. 

Indication: 

 

5 High intensity LED’s; 1 green, 3 red/amber 
and 1 yellow (“Low battery”)   

Fault-permanent

: All 5 LED’s flash every 5 sec. 

 

 

(10 sec after 12 hours) 

Fault-transient

: 1 green LED flash (every 5/10s) 

Low battery

: Yellow LED flash every 10s to 

 

 

indicate < 20% capacity left  

Intensity: 

> 12 Lumens 

Ambient & storage temp.: -40º 

 +85oC. 

Weight:      460 grams. 

Standards:   Conform to IEC 68-2. 

Tested according to: 

 

EN 61000-6-3 Generic standard – 
Emission industrial environments 

 

EN 61000-6-2 Generic standard – 
Immunity for industrial environments 

 

IEEE 495-1986 §4.4.8 

 
LT-110Eµr w/integr.Short Range Radio:  
 
The radio transmit a status telegram to the  
Collector (ComTroll 110C/115C or other)  
every 10 sec; containing Permanent or 
transient faults, low battery warning and 
Heart Beat. 
Frequency:  ISM band,  2.4 GHz 
Output: 1mW (0dBm), range: up to 20m*) 
Line Of  Sight (LOS).  
*) Margin = 20dB, with a Receiver 
sensitivity = -90dBm (=CmT 110C/115C). 
Longer distance may be achieved by taken 
special action when mounting and 
positioning the antenna and the indicators. 
 

Summary of Contents for LineTroll 110Em

Page 1: ...LINETROLL 110E 110E r User Guide February 2010 Page 1 of 16 LineTroll 110E LineTroll 110E r User Manual...

Page 2: ...3 Transient fault 8 4 4 Fused lines 8 4 5 Multiple faults 8 4 6 Capacitive discharges 9 4 7 PROGRAMMING 10 4 7 1 Di dt sensing 10 4 7 2 Threshold sensing 10 4 7 3 Start Stop criteria 10 4 7 4 Timer re...

Page 3: ...nd the fault or in the non damaged phase s remain idle Upon detecting a fault on the line the indication by means of an intermittent LED flash 3 red LED s and 1 amber LED indication for permanent faul...

Page 4: ...itches inside the unit In order to avoid activating the indicator due to the magnetising inrush current of the line it s di dt sensor is blocked for 5 sec upon re energising of the line While the bloc...

Page 5: ...When the unit is activated approximately 4 mA are consumed giving more than 1500 hours of flashing capacity The battery is fitted with a connector for simple replacement Figure 3 Initial battery capac...

Page 6: ...cause confusion since there may be an indication in a branch due to a non permanent fault while another branch without indicator may be faulty yet considered healthy Near line points with sectionalise...

Page 7: ...the blocking time a shows the sequence when a fault occurs less than 5 sec after line has been energised No Indication If upon re energising of the line the unit is indicating due to a previous fault...

Page 8: ...e of the fault If there is one disconnection within 5 sec followed by an automatic reclosing causing a fuse operation the indication starts but will reset after 30 sec If the automatic reset is switch...

Page 9: ...rrent of all the branches downstream the indicator is added Underground cables have larger capacitance than overhead lines This has to be taken into account when an overhead line feeds an underground...

Page 10: ...e 2 Threshold setting 4 7 3 Start Stop criteria 4 Start Stop criteria 0 Current 1 Voltage Table 3 Start Stop criteria 4 7 4 Timer reset 5 6 Timer reset 0 0 2 hours 0 1 6 hours 1 0 12 hours 1 1 24 hour...

Page 11: ...st be reset This is done by short circuiting the two pads on the underside of PCB while at the same time powering the indicator by connecting the battery The indicator will now confirm with continuous...

Page 12: ...ed LT 110E 30 40 A LT 110E r 300 A Activated flashing 4 mA Battery 3 6 V 16 5Ah type KBB 11 Recommended battery replacement approx every 10 years 5 years for LT 110E r or every 1500 operational hours...

Page 13: ...tworks Locate the indicators at strategic points along the line 9 1 Before mounting Make sure the indicator is programmed see 4 7 Programming and battery connected before mounting on the line 9 2 Live...

Page 14: ...r will in addition transmit a Low Battery message Programming Open the indicator by unscrewing the top cap from the lens See Figure 17 Pull out the electronics board just as far as to enable operation...

Page 15: ...sient fault Permanent fault GREEN RED Comments The Permanent Fault indication red LED s is delayed 70 sec to verify a permanent fault Both red and green LED s will flash on permanent faults until rese...

Page 16: ...energized or not Battery monitoring A Yellow LED will start flashing 1 10 Hz when remaining capacity is less than 20 to indicate that the battery should be replaced within the next 6 months f 1 10s 2s...

Reviews: