Page 30 of 34 Equipment replacement
553-2601-500A
Standard 2.0
December 1994
Procedure 15
QUD24 Cooling Unit replacement
Note: QUD24 cooling units are located in the cabinet top panel
assembly. Connections given in this chart are typical and may vary
from one installation to another. Cooling units are connected in series.
1
Remove the six screws securing the cabinet top panel assembly and
remove top (
2
Disconnect cable from P1 connector of QUD24 unit (
3
Disconnect the cable or terminating plug (whichever is equipped) from
connector P2 of the QUD24 unit (
4
Remove mounting screws securing QUD24 unit to cabinet top panel
(
5
Unpack and inspect the replacement QUD24 cooling unit.
6
Install replacement QUD24 unit and secure to cabinet top panel with
mounting screws (
7
Reconnect cable to connector P1 of the QUD24 cooling unit (
8
Reconnect cable or terminating plug (removed from previous QUD24
unit) to connector P2 of the QUD24 unit (
9
Reinstall cabinet top assembly and secure with mounting screws
(