Chapter 8 — Service changes and maintenance
553-3011-311
Standard 7.0
May 1999
5
Take the far-end ISDN BRI trunk DSL out of remote loopback mode
by entering the DSRB c dsl# command, and pressing the ENTER
key.
The the far-end and near-end ISDN BRI trunk DSLs are placed in the test
mode.
6
Take the far-end and near-end ISDN BRI trunk DSLs out of test
mode by entering the DSTS c dsl# command, and pressing the
ENTER key.
The ISDN BRI trunk DSLs are reset in their release or established state.
7
Enable the ISDN BRI trunk DSL by entering the ENLU command.
SILC fault isolation or UILC fault isolation and correction
The SILC and UILC intelligent peripheral cards provide eight S/T interfaces
and eight U interfaces respectively, which are used to connect ISDN BRI
compatible terminals or trunks over DSLs to the Option 11 system.
Procedure 8-6: Checking the SILC or UILC status
The diagnosis in Table 22 indicates that an SILC or a UILC may be faulty,
not equipped, or disabled. The first step in identifying the problem is to verify
the status of the card.
Summary of Contents for Meridian 1 Option 11C
Page 2: ......
Page 4: ...553 3011 311 Standard 7 0 May 1999...
Page 12: ...viii Contents 553 3011 311 Standard 7 0 May 1999...
Page 14: ...Page x About this guide 553 3011 311 Standard 7 0 May 1999...
Page 166: ...Page 152 of 492 Chapter 4 Network clocking 553 3011 311 Standard 7 0 May 1999...
Page 318: ...Page 304 of 492 Chapter 6 ISDN BRI trunk implementation 553 3011 311 Standard 7 0 May 1999...
Page 434: ...Page 420 of 492 Chapter 8 Service changes and maintenance 553 3011 311 Standard 7 0 May 1999...
Page 446: ...Page 432 of 492 Chapter 9 ISDN BRI traffic reports 553 3011 311 Standard 7 0 May 1999...
Page 492: ...Page 478 of 492 Appendix A 2Mb PRI implementation 553 3011 311 Standard 7 0 May 1999...