compressor
Data
Volts-Cycles-Phase (1)
208/230V, 1phase, 60Hz
Min. Circuit Ampacity (MCA)
16
21
28
33
Max. Overcurrent Protection (MOP)
25
35
45
50
Rated Load Amps (RLA)
12.8
16.6
21.8
26.2
Locked Rotor Amps (LRA)
58.3
79
117
134
Air Handler Match
B6EMMN36K-B
B6EMMN36K-B
B6EMMN60K-C
B6EMMN60K-C
Physical
Data
Length (L)
25.1
25.1
25.1
25.1
Width (W)
25.2
25.2
25.2
25.2
Height (H)
30.5
30.5
30.5
30.5
Weight
165
170
215
220
refrigerant Vapor line o.D.
(Both to air handler and earth loop)
3/4”
3/4”
7/8”
7/8”
liquid line o.D.
(Both to air handler and earth loop)
1/2”
1/2”
1/2”
1/2”
†† Unit is shipped from factory with nitrogen holding charge.
table 9. Electrical & Physical Data
Insulated
Liquid line
400 FT
(122 M)
Max Depth
Grout
Torpedo
Suction line
Borehole filled
with Grout 111
Frost Line
Figure 8. Vertical Borehole with Earth Loop