background image

4

electrical Wiring

 Warning:

electrical ShocK or Fire haZard

to avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. the 

unit may have more than one electrical supply.
label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause improper 

and dangerous operation

•  All electrical connections must be in compliance with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For  Canadian  installations  the  electrical  connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

pre-electrical checklist

 Verify that the voltage, frequency, and phase of the 

supply source match the specifications on the unit rating 

plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. See 

Figure 7, (page 10)

 & 

Figure 8, (page 

11)

. Inspect for loose connections.

line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 

become familiar with the wiring diagram before making 

any electrical connections to the outdoor unit.

• 

an electrical disconnect must be located within sight 

of and readily accessible to the unit. This switch shall 

be capable of electrically de-energizing the outdoor unit.

•  Line  voltage  to  the  unit  should  be  supplied  from  a 

dedicated branch circuit containing the correct fuse 

or circuit breaker for the unit. Incoming field wiring 

and minimum size of electrical conductors and circuit 

protection must be in compliance with information listed 

on the outdoor unit data label. Any other wiring methods 

must be acceptable to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagram / 

schematic for identification and location of outdoor unit 

field wiring interfaces. See 

Figure 7

 & 

Figure 8

. Make all 

electrical connections in accordance with all applicable 

codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. 

See the unit rating plate for minimum circuit ampacity 

and maximum overcurrent protection limits.

connecting refrigerant tubing Between 
the indoor & outdoor unit

 caution:

When servicing, cover or seal openings to 

minimize the exposure of the refrigerant system 

to air to prevent accumulation of moisture and 

other contaminants.

After outdoor and indoor unit placement has been 

determined, route refrigerant tubing between the 

equipment in accordance with sound installation practices.
•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through the 

joints during brazing to prevent internal oxidation and 

scaling.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. If precise forming of refrigerant lines is 

required, a copper tubing bender is recommended. 

Avoid sharp bends and contact of the refrigerant lines 

with metal surfaces.

•  Refrigerant  tubing  should  be  supported  in  a  manner 

that the tubing will not vibrate or abrade during system 

operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure 

that the field installed refrigerant containing components 

of the system have been installed in accordance with 

these instructions and sound installation practices to 

insure reliable system operation and longevity.

•  The maximum recommended interconnecting refrigerant 

line lengths is 75 ft. and the vertical elevation difference 

between the indoor and outdoor sections should not 

exceed 20 ft.

•  A  filter  dryer  is  provided  with  the  unit  and  must  be 

installed in the liquid line of the system. If the installation 

replaces a system with a filter dryer already present 

in the liquid line, the filter dryer must be replaced with 

the one supplied with the unit. The filter dryer must be 

installed in strict accordance with the manufacturer’s 

installation instructions.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 

with the manufacturer’s installation instructions.

Summary of Contents for S6BF-024 Series

Page 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Page 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Page 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Page 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Page 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Page 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Page 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Page 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Page 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Page 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Page 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Reviews: