background image

8

code agency listed conduit and a conduit connector for 

connecting the supply wires to the unit. Use of rain tight 

conduit is recommended.

•  See the unit wiring label for proper high and low voltage 

wiring. Make all electrical connections in accordance 

with all applicable codes and ordinances. See 

Figure 

15 (page 16)

,

 Figure 16 (page 17)

, & 

Figure 17 

(page 18)

.

Overcurrent Protection

Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. 

Generally, the best fuse or breaker for any heat pump 

is the smallest size that will permit the equipment to run 

under normal usage and provide maximum equipment 

protection. Properly sized fuses and breakers also prevent 

nuisance trips during unit startup.

If a fuse blows or a breaker trips, always determine 

the reason. Do not arbitrarily install a larger fuse or 

breaker and do not, in any case, exceed the maximum 

size listed on the data label of the unit.

Blower Speed

For optimum system performance and comfort, it may 

be necessary to change the factory speed setting. See 

Table 2

 for factory settings. 

NOTE

: This model has a High 

Efficiency ECM Motor with 5 speed taps.

 WARNING:

To avoid electric shock, personal injury, or death, 

turn off the electric power at the disconnect or the 

main service panel before making any electrical 

connections.

1. Disconnect all electrical power to the unit and remove 

the service panel.

 CAUTION:

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify proper 

operation after servicing.

2. Locate  the 

orange

red

 and 

blue

 wires terminated to 

the blower motor. The 

orange

 wire controls the low 

speed cooling and heating operations, the 

blue

 wire 

SUPPLY WIRE

LENGTH (FEET)

SUPPLY

CIRCUIT

AMPACITY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

Table 1. Copper Wire Size AWG (1% voltage drop) 

Table 2. Airflow Data

MODEL

NUMBER

MOTOR

TAP

EXTERNAL STATIC PRESSURE DROP (IN WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE CFM

HEAT

RISE

X24K

Tap T1*

686

46

651

49

621

51

589

54

530

60

477

-

431

-

382

-

Tap T2**

926

34

884

36

861

37

827

38

785

40

734

43

676

47

622

51

Tap T3***

1184

27

1161

27

1134

28

1109

28

1075

29

1041

30

1002

32

962

33

Tap T4

1383

23

1360

23

1330

24

1303

24

1277

25

1246

25

1215

26

1137

28

Tap T5

1537

21

1510

21

1487

21

1459

22

1437

22

1412

22

1382

23

1350

23

X36KA

Tap T1*

1004

31

972

33

938

34

897

35

845

37

779

41

739

43

668

47

Tap T2***

1167

27

1132

28

1100

29

1061

30

1020

31

979

32

921

34

851

37

Tap T3**

1355

23

1320

24

1282

25

1247

25

1209

26

1168

27

1121

28

1066

30

Tap T4

1510

21

1477

21

1441

22

1403

23

1366

23

1330

24

1288

25

1243

25

Tap T5

1648

19

1614

20

1578

20

1544

20

1512

21

1473

21

1434

22

1393

23

X48K

Tap T1*

1108

29

1063

30

1031

31

987

32

939

34

894

35

850

37

808

39

Tap T2***

1108

29

1063

30

1031

31

987

32

939

34

894

35

850

37

808

39

Tap T3**

1666

19

1629

19

1587

20

1572

20

1542

20

1507

21

1477

21

1431

22

Tap T4

1884

17

1824

17

1795

18

1762

18

1730

18

1707

19

1671

19

1634

19

Tap T5

1979

16

1948

16

1925

16

1892

17

1861

17

1834

17

1804

18

1766

18

X60K

Tap T1***

923

34

875

36

799

40

735

43

677

47

623

51

579

55

543

58

Tap T2*

1335

24

1295

24

1259

25

1214

26

1183

27

1144

28

1117

28

1063

30

Tap T3

1754

18

1721

18

1684

19

1660

19

1634

19

1597

20

1568

20

1541

21

Tap T4**

2045

15

2022

16

1983

16

1950

16

1921

16

1894

17

1869

17

1826

17

Tap T5

2253

14

2218

14

2187

14

2153

15

2117

15

2091

15

2057

15

2021

16

* Denotes factory set low cooling & heating speed
** Denotes factory set high cooling & heating speed
*** Denotes factory set auxillary heating speed

NOTE:

 Temperature rises shaded in gray are for reference only. These conditions are not recommended.

Summary of Contents for PPH3RF Series

Page 1: ...n important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes requir...

Page 2: ... Test Pins 10 Clearing Defrost Board Fault Codes 10 Electric Heat Package optional 10 Outdoor Thermostat Options 10 HUD Outdoor Thermostat Option 10 2nd Stage Thermostat Option 10 STARTUP ADJUSTMENTS 11 Pre Start Checklist 11 Start Up Procedure 11 Air Circulation 11 System Heating 11 System Cooling 11 Short Cycle Protection 11 Emergency Heat 11 Forced Defrost Mode Field Test 11 Anti Short Cycle Ti...

Page 3: ...ancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung cancer Fiberglass wool may also cause eye irritation skin sensitization or other allergic responses in susceptible individuals Always wear goggles disposable gloves long sleeved shirt and appropriate...

Page 4: ...e installation of this type of equipment Local codes and regulations take precedence over any recommendations contained in these instructions Consult local building codes and the NationalElectricalCode ANSICI forspecialinstallation requirements Air Ducts must be installed in accordance with the standards of the National Fire Protection Association Standards for Installation of Air Conditioning and...

Page 5: ...ioningandVentilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA90B theseinstructions andallapplicable codes NFPA publications are available by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioni...

Page 6: ... is in a corner or under a table if a minimum two inch clearance is available 1 Start the installation from under the home by cutting a small hole in the sub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located on 16 centers leaving 14 3 8 between joists 2 After measuring the return air box approximately ...

Page 7: ...ctrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit Line Voltage It is recommended that the line voltage to the unit be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This switch sh...

Page 8: ... 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 1 Copper Wire Size AWG 1 voltage drop Table 2 Airflow Data MODEL NUMBER MOTOR TAP EXTERNAL STATIC PRESSURE DROP IN WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CF...

Page 9: ...ric heating operation CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any metal components of the unit 3 Verify the required speed from the airflow data found in Table 2 page 8 Place appropriate wire on the appropriate motor speed tap for the required airflow 4 Check all factory wiring per the unit wiring diagram and inspect the f...

Page 10: ... soon as the jumper is removed the defrost cycle will end as determined by the typical criteria To determine operating status or fault conditions refer to Table 3 for diagnostic description Clearing Defrost Board Fault Codes Fault codes can be removed from memory through the use of the test pins This is accomplished by shorting the two test pins momentarily more than 1 second while there is no Y1 ...

Page 11: ... supply registers System Cooling Set the thermostat s system mode to COOL and the fan mode to AUTO Change the thermostat temperature selector below the existing room temperature Allow the cooling system to operate for several minutes and check for the discharge of cool air at the supply registers Short Cycle Protection The control circuit is equipped with a time delay feature for protection agains...

Page 12: ...ing of each heating and cooling season or more frequently if required Inspect the condensate drain and outdoor coil at the beginning of each cooling season Remove any debris Clean the outdoor coil and louvers as necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as neces...

Page 13: ...rigerant when below curve Remove refrigerant when above curve Figure 11 Charging Chart for 3 Ton Units Figure 10 Charging Chart for 2 Ton Units Liquid Temperature Deg F 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Q7RF X24K Charging Chart Cooling Remove refrigerant when above curve Add refrig...

Page 14: ...refrigerant when above curve Add refrigerant when below curve Figure 13 Charging Chart for 5 Ton Units Figure 12 Charging Chart for 4 Ton Units Liquid Temperature Deg F 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Remove refrigerant when above curve Add refrigerant when below curve Q7RF X48K ...

Page 15: ...01 1 75 Ø Electric Heater Power Supply 1 125 Ø Power Supply 0 875 Ø Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B X24K 49 35 30 2 29 00 2 48 X36KA 49 35 38 2 35 02 2 48 X48K 63 35 38 2 35 02 2 48 X60K 63 35 38 2 35 02 2 48 Table 4 Physical Data ...

Page 16: ...G DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour utili...

Page 17: ...ower before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour utiliser les fils conducteurs adapté à ...

Page 18: ...NG DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour util...

Page 19: ...19 ...

Page 20: ...lowthemanufacturer srefrigerant chargingandairflowinstructions Failuretoconfirm proper charge and airflow may reduce energy efficiency and shorten equipment life INSTALLATION ADDRESS CITY STATE UNIT MODEL UNIT SERIAL INSTALLER NAME CITY STATE Unit installed minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with the customer YES NO Has the literature package been l...

Reviews: