background image

12

charging the unit in Ac Mode

(with Outdoor Temperatures Above 65° F)

1. With the system operating at steady-state, measure 

the suction and liquid refrigerant pressures (in psig) at 

the service valves.

2. Measure the compressor discharge temperature (° F).

3. Use 

Table 4 (page 14)

Table 5 (page 14)

Table 6 

(page  15)

Table 7 (page 15)

Table 8 (page 16)

or 

Table 9 (page 16)

 to verify system conditions 

(during cooling mode) for proper charge amount.

charging the unit in Heating Mode

1. Evacuate the refrigerant system.

2. Use 

Table 10 (page 17)

Table 11 (page 17)

Table 

12 (page 17)

Table 13 (page 18)

Table 14 (page 

18)

, or 

Table 15 (page 18)

, as a guide and weigh 

in the proper charge as shown on the unit rating plate 

(during heating mode operation). 

notE:

 Unit charge 

MUST be verified in cooling season.

3. Verify the unit is operating properly according to the 

System Heating section on 

page 11

.

Safety Switches

•  The low pressure switch (if equipped) is factory installed 

and located in the suction line internal to the unit. The 

switch is designed to protect the compressor if a loss 

of charge occurs. Under normal conditions, the switch 

is closed.

  If the suction pressure falls below 5 psig, then the switch 

will open and de-energize the unit. The switch will close 

again once the suction pressure increases above 20 

psig. The low pressure switch interrupts the thermostat 

inputs to the unit. 

notE:

 When the switch opens and 

then closes, there will be a 5 minute short cycling delay 

before the unit can energize.

•  The high pressure switch is factory installed and located 

in the compressor discharge line internal to the unit. 

The switch is designed to de-energize the system when 

very high pressures occur during abnormal conditions. 

Under normal conditions, the switch is closed.

If the discharge pressure rises above 650 psig, the switch 

will open and de-energize the unit. The switch will close 

again once the discharge pressure decreases to 460 

psig. The high pressure switch interrupts the thermostat 

inputs to the unit. 

notE:

 When the switch opens and then 

closes, there will be a 5 minute short cycling delay before 

the unit can energize.

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using 

a mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

 cAutIon:

the unit should never be operated without a 

filter in the return air system. Replace disposable 

filters with the same type and size.

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed 

at the factory and does not require lubrication.

Adjustment of Refrigerant charge

 cAutIon:

this heat pump contains liquid and gaseous 

refrigerant under pressure. Adjustment of 

refrigerant charge should only be attempted 

by qualified, trained personnel thoroughly 

familiar with the equipment and safe responsible 

refrigerant handling procedures. under no 

circumstances should the homeowner attempt 

to install and/or service this equipment. Failure 

to comply with this warning could result in 
equipment damage, personal injury, or death.

Summary of Contents for PPH3RE Series

Page 1: ...lays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings coul...

Page 2: ...ing 11 Short Cycle Protection 11 Emergency Heat 11 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 Unit MAINTENANCE 11 Adjustment of Refrigerant Charge 12 Charging the Unit in AC Mode 1...

Page 3: ...ancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung...

Page 4: ...practical place the heat pump and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest Consideration should also be given to availability of electric po...

Page 5: ...tandards of the National Fire Protection Association StandardforInstallationofAirConditioningandVentilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Condit...

Page 6: ...re tight Homes with multiple supply ducts or special applications a Y fitting is available for dividing the supplyairtodifferentareasofthehomeformoreefficient cooling NOTE Formaximumperformance insula...

Page 7: ...ocation 2 Cut a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the...

Page 8: ...nside the control compartment Extend leads through power wiring hole See Figure 7 Connect L1 L2 directly to the contactor Use only copper wire for the line voltage power supply to this unit as listed...

Page 9: ...tinuously even through loss of power for 7 days Electric Heat Package optional This heat pump is shipped without an auxiliary electric heat kit installed If electric heat is desired an accessory heate...

Page 10: ...1630 1589 1545 048K T1 1418 1385 1351 1316 1279 1242 1203 1163 T2 1530 1500 1467 1433 1396 1358 1318 1275 T3 1679 1645 1611 1576 1541 1505 1469 1432 T4 1787 1757 1726 1693 1658 1621 1582 1542 T5 2006...

Page 11: ...for the discharge of warm air at the supply registers System Cooling Set the thermostat s system mode to COOL and the fan mode to AUTO Change the thermostat temperature selector below the existing roo...

Page 12: ...ernal to the unit The switch is designed to de energize the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rise...

Page 13: ...63 35 38 2 35 02 2 48 Figure 8 Physical Data Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View L W TopView 18 01...

Page 14: ...75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 133 249 131 135 250 134...

Page 15: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 135 26...

Page 16: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Page 17: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Page 18: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Page 19: ...N BLACK RED BLUE BLACK BLACK BLACK ORANGE RED YELLOW WHITE YELLOW GREEN WITH YELLOW STRIPE VIOLET WHITE 208 230 VOLT Z H 0 6 E S A H P E L G N I S P M U P T A E H D E G A K C A P L L A M S WIRING DIAG...

Page 20: ...LUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE BLACK YELLOW BLACK ORANGE RED YELLOW WHITE WHITE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ W...

Page 21: ...N BLUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE YELLOW ORANGE WITH YELLOW STRIPE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ WIRING DIAGRAM...

Page 22: ...ostat is used W2 OUT W2 IN Optional 2nd Stage Outdoor Thermostat Field Supplied 6 7 8 9 2 3 4 5 1 C G O W2 Y1 Y2 E R INDOOR TERMINAL THERMOSTAT White wire not present when optional thermostat is used...

Page 23: ...23...

Page 24: ...TY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO VENTING SYSTEM Is the ven...

Reviews: