Nortek 1RP24K Series Installation Instructions Manual Download Page 4

4

INSTALLATION/VERIFICATION OF THE 

SYSTEMS EXPANSION DEVICE

After outdoor and indoor unit placement has been determined, 

refer to the Quick Reference Data sheet for information on the 

appropriate TXV metering device to use for the equipment.  

Verify that the installed expansion device matches those 

requirements or install the correct expansion device.  Outdoor 

heat-pump units have the correct outdoor expansion device 

pre-installed at the factory. Verify that the TXV provided 

with the indoor unit matches the requirements in the Quick 

Reference Data. The correct expansion device or kit is 

available for all approved Nortek listed applications from 

the parts department.

Connecting Refrigerant Tubing Between the Indoor 

& Outdoor Unit

The SH3QE4M SERIES of units are equipped with single use 

quick-connect couplings. Together with the indoor section 

and an approved line-set, only four coupling connections are 

required to provide a 100% sealed system.  Pre-Charged 

Line-Set Kits of various lengths may be found in the technical 

sales literature for the unit.

•  Tubing and quick connect couplers should be kept clean 

of foreign debris during installation.

•  The SH3QE4M units are equipped with a factory installed, 

liquid line filter-drier within the outdoor unit.  Installers 

should ensure that only one filter-drier is installed in the 

liquid line of the system.

After outdoor and indoor unit placement has been determined, 

route refrigerant tubing between the equipment in accordance 

with sound installation practices.

• Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. If precise forming of refrigerant lines is 

required, a copper tubing bender is recommended. Avoid 

sharp bends and contact of the refrigerant lines with metal 

surfaces.

•  Refrigerant tubing should be supported in a manner that the 

tubing will not vibrate or abrade during system operation.

•  Every effort should be made by the installer to ensure that 

the field installed refrigerant containing components of 

the system have been installed in accordance with these 

instructions and sound installation practices to insure 

reliable system operation and longevity.

•  The maximum recommended interconnecting refrigerant 

line lengths is 75 ft. and the vertical elevation difference 

between the indoor and outdoor sections should not exceed 

20 ft.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 

with the manufacturer’s installation instructions.

Coupling the Line-Set to the Unit

Nortek approved line-sets are factory sealed assemblies, 

vacuumed properly and pre-charged with a refrigerant holding 

charge. Always verify that the refrigerant within the line-set 

matches the refrigerant called out on the unit nameplate.

It is recommended to only work on and complete one quick-

connection coupling at a time. After the line-set has been 

properly routed between the units, prepare the couplers and 

connect them in accordance with the following.

1) Inspect the outside of the couplings and ensure that they 

are free of any dirt or debris.  Clean, if necessary.

2) Remove the protective caps and plugs from the couplings to 

be joined.  Inspect the interior of the coupling.  If necessary, 

clean the interior of the coupling with a clean, soft, lint-free 

rag or cloth.  Ensure that o-ring is in place and that the 

threads are clean and undamaged.

3) Apply clean refrigerant oil to the entire surface of the 

diaphragm, o-ring and threaded area of the male coupling 

assembly. The amount of lubricant used must cover all 

designated surfaces sufficiently. Ideal application is a 

small brush with lubricant applied liberally. As an alternate, 

another acceptable lubricant would be a refrigerant 

compatible silicone grease product similar to Dow Corning 

DC200/60,000 cst. Nortek approved line-set kits include 

a packet of silicone grease for use.

4) Ensure that the couplers to be joined are properly aligned 

with each other. The end faces of the couplers should be 

parallel with each other and visually in-line down the center 

axis of the couplers. By hand, start threading the nut on the 

female coupler onto the male for 2-3 full thread rotations 

of the union nut. This should bring the diaphragm of both 

couplers into contact with each other. A sharp increase in 

torque will be felt when they come into contact.

If the nut will not start by hand, or if it is difficult to rotate 

the union nut by hand, adjust the position of the line-set 

coupler to improve the alignment between the couplers. 

There should be no side-load on the coupling during 

assembly. DO NOT Proceed to the next step until any 

misalignment is corrected and the union nut can easily 

be threaded by hand.

5) Refer to table 1 for the appropriate wrench sizes and torque 

values for the coupling being connected.

Once this operation is begun, the coupling seals will be 

pierced, and the units’ refrigerant will be released into 

the line.  During the tightening operation, the o-ring seal 

will prevent any refrigerant from escaping. However, if 

for any reason it is decided to disassemble the coupling 

after beginning this operation, the refrigerant charge will 

need to be recovered from the unit and the line prior to 

doing so.

Using both a back-up wrench on the female body of the 

coupling and primary wrench on the female union nut, 

tighten the union nut.  Ensure that the female coupler body 

does not rotate with respect to the male coupler during the 

tightening operation.  The nut should be tightened until a 

definite increase in resistance is felt.  This will be the metal 

to metal contact of the permanent sealing surfaces.  At this 

point, the union nut will have covered all, or mostly all threads 

on the male coupler body.  (Some larger coupler sizes may 

show approximately 1/2 of the last thread when properly 

assembled.)  Refer to the figure below for additional detail.

COUPLING

SIZE

TORQUE

MALE

COUPLING

FEMALE

COUPLING

NUT

FEMALE

COUPLING

BODY

3/8”

(10mm)

10-12 Ft-Lbs

(14-16 Nm)

3/4”

13/16”

5/8”

3/4”

(19mm)

35-45 Ft-Lbs

(47-61 Nm)

1-1/16”

1-5/16”

1”

7/8”

(22mm)

35-45 Ft-Lbs

(47-61 Nm)

1-1/8”

1-5/16”

1”

Table 1. Torque Values

Summary of Contents for 1RP24K Series

Page 1: ...mer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 HEAT PUMP INSTALLATION 3 General Information 3 Before You Install this Unit 3 Packaging Removal 3 Locating the Heat Pump 3 Clearance Requirements 3 Ground Level 3 Roof Mount 3 Accessory Mounting Kits 3 INSTALLATION VERIFICATION OF THE SYSTEMS EXPANSION DE...

Page 2: ... the instructions provided with the equipment priortoperformingtheinstallationandoperationalcheckout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is designed for outdoor installations only and should be positioned as shown on page 3 IMPORTANT SAFETY INFORMATI...

Page 3: ...ine the best location for mounting the outdoor unit Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ventilated areas and areas subject to accumulation of debris should be avoided The unit should not be placed under roofing or othe...

Page 4: ...rs and connect them in accordance with the following 1 Inspect the outside of the couplings and ensure that they are free of any dirt or debris Clean if necessary 2 Removetheprotectivecapsandplugsfromthecouplingsto bejoined Inspecttheinteriorofthecoupling Ifnecessary clean the interior of the coupling with a clean soft lint free rag or cloth Ensure that o ring is in place and that the threads are ...

Page 5: ... the refrigerant system to air to prevent accumulation of moisture and other contaminants CAUTION When connecting refrigerant line sets together it is highly recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling Copper oxides internal to the system can damage the compressors bearings and seals block small orificesandmicrochannelsorothe...

Page 6: ...n device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided external to the outdoor unit Use only gage line sets which have a Schrader depression device present to actuate the valve An automatic high pressure switch is factory installed installed in these units and is located on the discharge l...

Page 7: ... outdoor unit field wiring interfaces Figure 7 page 12 and Figure 8 page 13 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA and maximum o...

Page 8: ...nepressureis530psigorgreater thentheHeatPump Mild Weather Control Kit is required to be installed on the system Alternately the control system could be configured to utilize the emergency or auxiliary heating means in order to maintain reliable system operation Air Circulation Indoor Blower 1 Set the thermostat system mode on OFF and the fan mode to ON 2 Verify the blower runs continuously Check t...

Page 9: ...then REMOVE refrigerant If your measured superheat at the suction valve isGREATERTHANtherecommendedsuperheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table th...

Page 10: ...iquid valve is LESSTHANtherecommendedsubcoolingvalue in the table then ADD refrigerant If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant If the outdoor temperature is below 35 degrees F After completing the refrigerant line connections leak checking the system and evacuating the indoor section and all line connecti...

Page 11: ...d Figure 6 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit motors are manufactured with sealed permanently lubricated bearings that are designed for the life of the equipment without ...

Page 12: ...s that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant d...

Page 13: ...ound 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring shall NOT be grounded to this unit 1 Couper le courant avant de faire letretien 2 Employez ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...allon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPO...

Reviews: