background image

 

 

2553860--B| 22 July 2014 

 

                                   Introduction |

 1

 

Outdoor Mount Temperature Sensor Installation Instructions 

 

This document covers the operation and installation instructions for the following Nortec Digital Humidity Controllers: 
Part #:    

Description: 

1510142 

  0-10V Digital Wall Humidistat 

2520259 

On/Off Digital Wall Humidistat 

2520266 

0-10V Digital Duct Humidistat pkg. 

2520273 

On/Off Digital Duct Humidistat pkg. 

2548731 

Nortec Digital Wall ON/OFF Humidistat pkg. 

2548732 

Nortec Digital Duct ON/OFF Humidistat pkg. 

 

 

Installation 

Outside air probes must be installed on a flat vertical surface protected from direct sunlight and rain.  

 

The cable gland must face downwards. 

 

To install the sensor, remove cover 

 

Place seal and washer below the long mounting screw. Securely fix it to wall.  

 

Thread wires through cable gland or conduit connector 

 

Connect the wires, normally 18ga unshielded twisted pair, according to the wiring diagram to the measuring circuit in the cover:  

 

Tighten cable gland 

 

Assemble the cover with the base plate. Make sure the seal in the seal grove of the cover is not damaged and in place. 

 

Tighten the four screws of the cover with moderate torque to complete the installation. 

 

 

Technical Specification 

Sensing Probe 

 Thermistor: 

Accuracy:  -40…0°C (-40…32°F):  
 

0…50°C (32…122°F):  

 

50…100°C (122…212°F):  

NTC 
0.5 C 
0.2 C 
0.5 C 

Connection 

Terminal Connectors 

For wire AWG 24…12 

Environment 

Operation 

Temperature 
Humidity 

To IEC 721-3-3 
-40…100°C (-40…212°F) 
<95% R.H. non-condensing 

 

 

 

Standards 

conform according to  

EMC Standard 89/336/EEC 
EMEI Standard 73/23/EEC 

 
EN 61 000-6-1/ EN 61 000-6-3 

Product standards 

Automatic electrical controls for household 
and similar use 
Special requirement on temperature 
dependent controls 

 
EN 60 730 –1 
 
EN 60 730 – 2 - 9 

Degree of Protection 

IP65 to EN 60 529 

Safety Class 

III (IEC 60536) 

Housing  

Material 

Fire proof PC + ABS plastic 

Dimensions  

Cover: (H x W x D)  

33 x 60 x 50 mm (1.3 x 2.4 x 2 in) 

Weight (including package) 

80 g (2.8 oz) 

 

50 (2) 

60 (2.4) 

33

 (

1.

3

 

Figure 1:  Dimensions 

 