TERMINAL BLOCK -- UNIT PANEL

R7TQ 090/120:  AK20 - AMS6

 DWG #1011728  SHT. #1

L1

L3

 3
 5
 7
 7
 8
 8

10
16
20

21

22
36
37
38
39
40

41

46
48
50

51

52
53
54
72

WIRING CODE

BLACK - BK
BROWN - BR

RED - RD

ORANGE - OR
YELLOW - YE
GREEN - GN
BLUE - BL
VIOLET - VI
WHITE - WH

TERMINAL BLOCK -- UNIT PANEL

L1

L2
L3

    A TEMPERATURE RATING OF AT LEAST 105 DEGREES C.,

    MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

2.  CAUTION:  IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

3.  LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE OF A SIZE

    TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

                                NOTES

     TIMES THE MAXIMUM TOTAL INPUT AMPS.

     LINE FEEDS CONNECT TO THE LOCKABLE DISCONNECT OR DISTRIBUTION BLOCKS.

     USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

 7.  ALL MOTORS MARKED IOL HAVE INTERNAL LINE BREAK.

 6.  WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

 5.  USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

 4.  SEE RATING PLATE LABEL FOR MCA, TO DETERMINE LINE FEED COPPER WIRE SIZE.

 8.  FUSIBLE DISCONNECT IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.
 9.  THE LINE SIDE OF THE DISCONNECT SWITCH MUST BE CONNECTED TO THE INCOMING

    POWER SUPPLY SUCH THAT THE VOLTAGE BETWEEN L1 AND GROUND IS THE GREATER VALUE.

GRAY - GY

 (LOW VOLTAGE SECTION)

 (HIGH VOLTAGE SECTION)

           FIELD CONTROL WIRING

 350 FEET                   #14 GA.

 250 FEET                   #16 GA.

 150 FEET                   #18 GA.

  LENGTH                  WIRE SIZE

TOTAL WIRE      MINIMUM RECOMMENDED

FIELD WIRING

FACTORY WIRING

1.  DISCONNECT ALL POWER BEFORE SERVICING.

DSI BOARD LED's

LED STATE

COLOR               CODE

GREEN         STEADY ON

GREEN         FAST FLASH

GREEN          1 FLASH

GREEN          2 FLASHES

GREEN          3 FLASHES

GREEN          4 FLASHES

GREEN         STEADY OFF

YELLOW       STEADY ON

YELLOW       SLOW FLASH

YELLOW       FAST FLASH

NORMAL OPERATION NO CALL FOR HEAT

NORMAL OPERATION CALL FOR HEAT

IN LOCKOUT FROM FIELD IGNITIONS OR FLAME LOSSES

PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS
OF VENTER ENERGIZED

LIMIT SWITCH OPEN

PRESSURE SWITCH IS CLOSED BEFORE VENTER IS 

INTERNAL CONTROL FAULT OR NO POWER

FLAME SENSED

WEAK FLAME

UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)

ENERGIZED

REFER TO DRAWING # 1011991 FOR STANDARD PLUG & ECONOMIZER PLUG CONNECTION