background image

9

Use a separate branch electrical circuit for this
unit.  A means of electrical disconnect must be
located within sight of and readily accessibility
to the unit.  Internally mounted circuit breakers
are available as field installed options.  These
circuit breakers can be used as an electrical
disconnect.

Provide power supply (or supplies) for the unit in
accordance with the unit wiring diagram, and
the unit rating plate.  Connect the line-voltage
leads to the corresponding terminals on the
contactor (or the circuit breaker when the field
installed circuit breaker kits are used) inside the
control compartment.  Use only copper wire for
the line voltage power supply to this unit.  Use
proper code agency listed conduit and a conduit
connector for connecting the supply wires to the
unit and for obtaining proper grounding.
Grounding may also be accomplished by using
the grounding lug provided in the control box.

!

 WARNING:

The unit cabinet must have and
uninterrupted or unbroken electrical
ground to minimize personal injury if an
electrical fault should occur.  This
ground may consist of electrical wire or
approved conduit when installed in
accordance with existing national or
local codes.

Blower Speed — The blower speed is preset at
the factory for operation at the same speed for
heating and cooling.  For optimum system
performance and comfort, it may be necessary
to change the factory set speed.  To change the
blower speed:

1. Disconnect all electrical power to the unit

and remove the service panel.

2. Cut the wire tie holding the motor lead

bundle. See Figure 9 for detailed
information on the appropriate model and
speed desired.

3. If the desired heating blower speed is

different than the cooling speed, remove
and discard the jumper wire between
terminals #6 and #4. on the blower relay.
Place the desired heating blower speed
lead on terminal #6 and the desired
cooling blower speed lead on terminal
#4 of the blower relay. Use another wire
tie (field supplied) to bundle the
remaining motor leads.

!

 CAUTION:

To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated metal components of
the unit.

Check all factory wiring per the unit wiring
diagram and inspect the factory wiring
connections to be sure none loosened during
shipping or installation.

Low Voltage Connections

Room Thermostat — Several options are avail-
able for a room thermostat depending on the
accessories installed with the unit.  The avail-
able thermostats recommended for use with the
Q4 units are listed with the accessories in Table
5.  Select a thermostat which operates in con-
junction with the installed accessories.  The
thermostat should be mounted about five feet
above the ground on an inside wall.  The ther-
mostat should be kept away from drafts, slam-
ming doors, lamps, direct sunlight, or in line with
the supply air flow.

To install the thermostat:

1. Position the sub base on an inside wall and

mark the mounting holes and thermostat
cable openings.

2. Cut out the cable opening and route the

thermostat cable from the unit’s low voltage
compartment  to the thermostat location.
The thermostat cable is supplied by the
installer.

3. Connect the cable leads to the sub base or

thermostat terminals and to the unit’s low
voltage pigtails as shown in Figure 10.   A
system wiring diagram is also provided on
the inside of the control panel cover and in
Figure 8 of these installation instructions.

4. Secure sub base or thermostat to the wall

using screws provided with the thermostat.

5. If sub base is used, install the correct

thermostat housing to sub base.

6. Refer to thermostat instruction sheet for

complete detailed mounting information.

Defrost Cycle Timer — The defrost cycle timer
controls the time interval of the hot gas defrost
after the defrost sensor closes.  It is located in
the lower left corner of the defrost control board
on the low voltage side of the control box.  Three

Summary of Contents for Q4 Series

Page 1: ...ntended to assist qualified individuals experienced in the proper installation of heating and or air conditioning appliances Some local codes require licensed installation service per sonnel for this...

Page 2: ...ging and Hoisting 7 Rooftop 7 AIR DUCTS 7 Unconditioned Spaces 7 Acoustical Duct Work 8 Horizontal to Down flow Conversion 8 Clearance 8 ELECTRICAL WIRING 8 Line Voltage 8 Blower Speed 9 Low Voltage C...

Page 3: ...out the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat tran...

Page 4: ...and the outdoor fan off for approx imately six minutes following a previous operation or the interruption of the main electrical power Emergency Heat Some thermostats will include a system switch posi...

Page 5: ...inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consignee RequirementsandCodes Theinstallermust comply with all local codes and regulations which...

Page 6: ...View Center of Gravity Height in inches Model No C with base rails without base rails Q4SA 036 340 28 0 26 0 33 7 31 3 Q4SA 048 345 28 0 26 0 33 7 31 3 Q4SA 060 400 29 5 26 5 37 7 35 3 A B Unit Weight...

Page 7: ...ppropriate accessory roof curb and follow all instructions included with it Locate the unit accordingtolocalbuildingcodesandordinances The curb must be level to insure proper condensate drainage See F...

Page 8: ...ntal duct opening with the cap The insulation will be on the indoor side 4 Fasten the cover with screws and seal to prevent air leakage Clearance The Q4 Series is approved for 0 inch clearance Figure...

Page 9: ...desired cooling blower speed lead on terminal 4 of the blower relay Use another wire tie field supplied to bundle the remaining motor leads CAUTION To avoid personal injury or property damage make cer...

Page 10: ...the outdoor fan turns freely Verify that the power supply branch circuit overcurrent protection is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set t...

Page 11: ...owner attempt to install and or service this equipment Failure to comply with this warning could result in property damage personal injury or death CAUTION Use care when removing parts from this unit...

Page 12: ...Optional Check Thermostat Instructions Y2 W2 W3 X E R W2 O Y C DEFROST BOARD External Static Pressure Drop inches water column Model Speed 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Q4SA 036 High 1600 1510 1410...

Page 13: ...1 20 144 132 25 152 132 30 161 132 35 169 131 44 185 140 57 211 158 70 236 175 21 151 130 26 158 130 31 165 130 36 172 129 45 192 137 58 218 153 71 243 169 22 158 128 27 164 128 32 170 128 37 176 127...

Page 14: ...Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp 12 122 126 19 139...

Page 15: ...Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp 68 188 122 70 191 123 204 135 72 192 140 207 139 222 137 234 14...

Page 16: ...287 175 78 214 215 231 204 247 195 262 188 278 183 291 181 304 179 80 232 216 249 207 265 199 280 193 295 188 309 185 82 267 210 282 203 298 197 313 192 84 300 206 315 201 86 303 216 318 210 88 320 2...

Page 17: ...HP 2 stage htg 1 stage cool auto M brand 912931 T stat HP 2 stage htg 1 stage cool auto I brand 912929 T stat HP 2 stage htg 1 stage cool manual M brand 912932 T stat HP 2 stage htg 1 stage cool manu...

Page 18: ...ny of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rating of at least 105 C 4 For supply wire ampacities and overcurren...

Page 19: ...H N I S U I H A S B I D D A R I STAN A R 210 T A I D N FIED T R E C E EN R C O I I O N ING T AI D N R CO I I O N I N G D ITI O N I N G N O C R I A R 707885W 707885A St Louis MO 707885A Replaces 70788...

Reviews: