background image

11

Heating — Lower the thermostat setpoint 
temperature to the lowest obtainable setting and 
set the thermostat function switch to HEATING. 
The indoor blower and outdoor unit should stop 
running. After a minimum of five minutes, increase 
the setpoint temperature of the thermostat to the 
maximum setting. Verify that the outdoor unit and 
indoor blower have energized. Feel the air being 
circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen 
for any unusual noises. If present, locate and 
determine the source of the noise and correct 
as necessary.

OUTDOOR THERMOSTAT (if supplied)

The outdoor thermostat prevents the electrical 
auxiliary heat (if used) from operating above a 
desired set point. Selection of the set point is 
determined from the building design heat load.

The thermostat is adjustable from 45°F to 0°F. 
The factory temperature setting is at 40°F.

Defrost Cycle Timer — The defrost cycle timer 
controls the time interval of the hot gas defrost 
after the defrost sensor closes. It is located 
in the lower left corner of the defrost control 
board. Three interval settings are available: 30 
minutes, 60 minutes, and 90 minutes. Time setting 
selection is dependent on the climate where the 
unit is being installed. 

Example 1. Dry climate of Southern 
Arizona. A 90 minute setting is 
recommended.

Example 2. Moist climate of Seattle, 
Washington. A 30 minute setting is 
recommended.

To set the cycle timer, place the timing pin on 
the defrost control board to the desired time 
interval post. 

Note: All units are shipped from the factory with 
the default time setting of 30 minutes. Maximum 
heating performance can be achieved by setting 
the time to 90 minutes.
 
DEFROST CONTROL BOARD OPERATION 
AND TESTING

1. Terminals “R”-”C” must have 24±V present 

between them in order for the time delay and 
defrost sequences to be operational.

2. Jumper the “T2”-”DFT” test pins. This will 

indicate to the board that the defrost T-stat 
is closed(if the compressor is running). 
Defrost T-stat is closed at 32° or below and 
is open at 68° or above.  But it’s state is 
unknown if the temperature is between 32°F 
and 68°F.  The defrost thermostat tells the 
board whether a defrost cycle needs to be 
started or terminated.  With the DFT closed 
the unit will run for 30/60/90 minutes in heat 
mode and then defrost the outdoor coil.  The 
defrost will turn off the outdoor fan, turn on the 
compressor and raise the coil temperature to 
68°F.  This will open the DFT and terminate 
the defrost.  If the DFT does not open the 
defrost will end after 10 minutes.

Figure 2. Comfort Alert

TM

 Diagnostics Module

POWER LED

(Green)

TRIP LED

(Red)

ALERT LED

(Yellow)

Diagnostics

Key

Summary of Contents for DT4BE

Page 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Page 2: ...2...

Page 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Page 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Page 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Page 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Page 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Page 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Page 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Page 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Page 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Page 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Page 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Page 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Page 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Page 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Page 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Page 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Page 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Page 23: ...23...

Page 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Reviews: