background image

10

the thermostat inputs to the unit. Thus, when the 
switch opens and then closes, there will be a 5 
minute short cycling delay before the outdoor 
unit will energize.

High-Pressure Switch — A high-pressure 
switch is factory-installed and located in the 
compressor discharge line internal to the outdoor 
unit. The switch is designed to de-energize the 
system when very high pressures occur during 
abnormal conditions. Under normal conditions, 
the switch is closed. If the discharge pressure 
rises above 575 psig, then the switch will open 
and de-energize the outdoor unit. The switch 
will close again once the discharge pressure 
decreases to 460 psig. Please note that the switch 
interrupts the thermostat inputs to the unit. Thus, 
when the switch opens and then closes, there 
will be a 5 minute short cycling delay before the 
outdoor unit will energize.

Short Cycle Protection — With the system 
operating in COOLING mode, note the setpoint 
temperature setting of the thermostat, and 
gradually raise the setpoint temperature until 
the outdoor unit and indoor blower de-energize. 
Immediately lower the setpoint temperature of 
the thermostat to its original setting and verify 
that the indoor blower is energized and that the 
outdoor unit remains de-energized. Verify that, 
after approximately 5 minutes, the outdoor unit 
energizes and that the temperature of the air 
supplied to the facility is cooler than ambient 
temperature.

Comfort Alert

TM

 Diagnostics (Select Models) 

—  The Comfort Alert

TM

 diagnostics module 

facilitates troubleshooting heat pump and air 
conditioning system failures. This Comfort 
Alert

TM

 module is designed only for single-phase 

systems with scroll compressors that have 
internal overload protection. By monitoring and 
analyzing data from the compressor and the 
thermostat demand, the module can detect the 
cause of electrical and system related failures 
without any sensors. A flashing LED indicator 
communicates the ALERT code and guides the 
service technician more quickly and accurately 
to the root cause of a problem.

NOTE:  This module does not provide safety 
protection! The Comfort Alert

TM

 module is a 

monitoring device and cannot control or shut 
down other devices.

LED Description (See Figure 2)
POWER LED (Green): indicates voltage is present 
at the power connection of the module.

ALERT LED (Yellow): communicates an 
abnormal system condition through a unique 
flash code. The ALERT LED will flash a number 
of times consecutively, pause and then repeat 
the process. The number of consecutive 
flashes, defined as the Flash Code, correlates 
to a particular abnormal condition. Detailed 
descriptions of specific ALERT Flash Codes are 
shown in Table 1 of this manual.

TRIP LED (Red): indicates there is a demand 
signal from the thermostat but no current to the 
compressor is detected by the module. The TRIP 
LED typically indicates the compressor protector 
is open or may indicate missing supply power 
to the compressor.

The scroll compressor’s run (R), common (C) 
and start (S) wires are routed through the holes 
in the Comfort Alert

TM

 module marked “R,” “C” 

and “S.”

24 VAC Power Wiring  — The Comfort Alert

TM

 

module requires a constant nominal 24 VAC 
power supply. The wiring to the module’s R and 
C terminals must be directly from the indoor unit 
or thermostat.

The Comfort Alert

TM

 module requires a thermostat 

demand signal to operate properly.

NOTE:  After the thermostat demand signal is 
connected, verify that 24 VAC across Y and C 
when demand is present.

TROUBLESHOOTING
Interpreting The Diagnostic LEDs – 
When 
an abnormal system condition occurs, the 
Comfort Alert

TM

 module displays the appropriate 

ALERT and/or TRIP LED will flash a number of 
times consecutively, pause and then repeat the 
process. To identify a Flash Code number, count 
the number of consecutive flashes.

Every time the module powers up, the last 
ALERT Flash Code that occurred prior to shut 
down is displayed for one minute. The module 
will continue to display the LED until the condition 
returns to normal or if 24 VAC power is removed 
from the module.

Cooling — Gradually lower the thermostat 
temperature setpoint below the actual room 
temperature and observe that the outdoor unit 
and indoor blower energize. Feel the air being 
circulated by the indoor blower and verify that it is 
cooler than ambient temperature. Listen for any 
unusual noises. If present, locate and determine 
the source of the noise and correct as necessary.

Summary of Contents for DT4BE

Page 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Page 2: ...2...

Page 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Page 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Page 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Page 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Page 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Page 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Page 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Page 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Page 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Page 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Page 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Page 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Page 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Page 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Page 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Page 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Page 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Page 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Page 23: ...23...

Page 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Reviews: