Pressure
Runup
Pressure Settings
Pressure Mode
OLED User Interface
38
Part 1128351_02
E
2020
Nordson Corporation
Pressure Runup Alert Threshold Settings
Enter
the maximum/minimum pressure thresholds you want the system to
use before
receiving an alert alarm.
NOTES
:
S
An Alert Alarm is generated if the maximum or minimum pressure is out of
tolerance for more than 10 seconds.
S
A “+” symbol appears next to the
High Pressure Alert threshold
setting
indicating the offset or delta from the
Maximum Pressure Set Point Range
setting.
S
A “-” symbol appears next to the
Low Pressure Alert threshold
setting
3indicating the offset or delta from the
Minimum Pressure Set Point Range
setting.
1. Select
Pressure Alert Threshold
, press
>
and enter the following
information:
S
High Pressure:
Pressure
Default
Minimum
Maximum
PSI
70
10
70
BAR
4.83
0.69
4.83
kPa
483
69
483
S
Low Pressure:
Pressure
Default
Minimum
Maximum
PSI
10
10
70
BAR
0.69
0.69
4.83
kPa
69
69
483
2. When done, press
<
to return to the
Runup Settings
menu or
to
return to the
Home
screen.