Fault indications / warning and fault list
Detailed information on the fault indication on the Nordmann SPA Display as well as a list of the warning
and fault messages which can occur during operation of the Nordmann Omega or the Condair Delta
SPA Control Box can be found in chapter 8 of the Nordmann Omega or the Condair Delta SPA Control
Box operation manual.
6.2
Malfunctions during operation of the Nordmann SPA Display
Malfunction
Cause
Remedy
Message "Time Out" appears in
the Nordmann SPA Display.
No data connection
Check connections "L" and "H" on
the Nordmann SPA display and
on the Nordmann Omega or the
Condair Delta SPA Control Box
control board.
Keystroke is not detected in the
correct location.
Display is not calibrated correctly. If possible, access the calibration
function (Path: Menu > Engineer-
ing > Admin > Display > Cali-
brate) and start the calibration
function by pressing "Start".
Other wise, the display must be
replaced.
Display remains dark.
Nordmann Omega or the Con-
dair Delta SPA Control Box is
not switched on.
Switch on the Nordmann Omega
or the Condair Delta SPA Control
Box.
No supply voltage present:
– Supply cable not or not cor-
rectly connected.
– Control board of the Nord-
mann Omega or the Condair
Delta SPA Control Box defec-
tive.
– Connect cable correctly.
– Check/replace control board
of the Nordmann Omega or
the Condair Delta SPA Control
Box.
No reaction when taping on a key
on the display.
SPA display defective.
Replace SPA display.
Control board of the Nordmann
SPA display defective.
Replace control board.
6
Troubleshooting