41
5.5
Water installation
5.5.1
Overview water installation
Fig. 15: Overview water installation for single units Small ("S") and Medium ("M")
Fig. 16: Overview water installation for double units Medium ("M ")
Filter valve (accessory) or
Shut-off valve and filter 125 µm
Water drain connector ø30 mm
Water supply connector G 3/4"
Water supply pipe
(min. inner diameter 8 mm, supplied by others)
Drain hose (supplied)
– internal diameter ø30 mm
– Drain hose must be led to the left
– constant downslope (min 15 %/8.5°) to funnel
– must not touch funnel
– if using DI or RO water, use supplied drain hose or stainless
steel pipe only
Open funnel with trap
(supplied by others)
ømin: 40 mm
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)
Filter valves (accessory) or
Shut-off valves and filters 125 µm
Water drain connectors ø30 mm
Water supply connectors G 3/4"
Water supply pipes
(min. inner diameter 8 mm, supplied by others)
Drain hoses (supplied)
– internal diameter ø30 mm
– Drain hoses must be led to the left
– constant downslope (min 15 %/8.5°) to collector pipe
– Fix drain hoses with hose clamp to the hose connectors
of the collector pipe
– if using DI or RO water, use supplied drain hose or stain-
less steel pipe only
Collector with hose connectors (ø30 mm) and drain pipe
(not supplied)
– Internal diameter drain pipe min. ø60 mm
– constant downslope (min 15 %/8.5°) to funnel
– Drain pipe of collector must not touch funnel
– if using DI or RO water, the collector pipe must be made
of stainless steel
Open funnel with trap, positioned on the left of left module
(supplied by others)
1...10 bar / 1...40 °C
(with optional drain water
cooling 2...10 bar / 1...25 °C)
ømin: 60 mm