26
5.4
Steam installation
5.4.1
Overview steam installation for duct humidification
Fig. 8: Overview steam installation for duct humidification
KS10
DS80
DV81
Steam line
– as short as possible (max. length 4 m)
– adequate upslope/downslope min.15 % (8.5°)
– no restrictions
– condensate trap at the lowest point
– hose or fixed pipe (with same inner diameter as
steam outlet)
Condsensate line
– min. downslope 15 % (8.5°)
– no restrictions
– condensate trap ømin 200 mm
ømin: 200 mm
Calculated absorption distance B
N
to any obstruction
or min. 3 m if B
N
is unknown
min. 5x B
N
(B
N
see
)
min. 300 mm
min. 300 mm
Pmax 1500 Pa
Pmin -1000 Pa
Rmin:
300 mm
to drain
to cylinder
Supply duct