External output isolation transformer connection

Parameter 2: Allow or disallow 

external output isolation transformer 

connection.

ENA:

 If selected, it’s allowed to 

connect to an external output isolation 

transformer.

DIS:

 If selected, it’s not allowed to 

connect to external output isolation 

transformer. (Default)

18: 

Display setting for autonomy time

Parameter 2: Set up the display setting 

for autonomy time 

EAT:

 If EAT is selected, it will display the 

remaining autonomy time. (Default)

RAT:

 If RAT is selected, it will show 

accumulated autonomy time so far. 

19: 

Acceptable input voltage range setting 

Parameter 2: Set the acceptable high 

voltage point and acceptable low 

voltage point for input voltage range by 

pressing the Down key or Up key.

HLS:

 Input high voltage point

280/290/300:

 setting the high voltage 

point in parameter 2. (Default: 300Vac)

LLS:

 Bypass low voltage point

110/120/130/140/150/160:

 setting 

the low voltage point in parameter 2. 

(Default: 110Vac)

00: 

Exit setting

Exit the setting mode.

Operating Mode Description

5.6

Operating 

mode

Description

LCD display 

Online mode

When the input voltage is 

within acceptable range, 

UPS will provide pure 

and stable AC power to 

output. The UPS will also 

charge the battery in 

online mode.

ECO mode

Energy saving mode: 

When the input voltage is 

within voltage regulation 

range, UPS will bypass 

voltage to output for 

energy saving. The UPS 

will also charge the 

battery at ECO mode.

Frequency 

Converter 

mode

When input frequency 

is within 40 Hz to 70 

Hz, the UPS can be set 

at a constant output 

frequency, 50 Hz or 60 Hz. 

The UPS will still charge 

battery under this mode. 

The capacity of the UPS 

should be derated to 80% 

when Frequency Converter 

mode is enabled.

Battery 

mode

When the input voltage 

is beyond the acceptable 

range or power failure, 

the UPS will backup 

power from battery and 

alarm is sounding every 5 

seconds.

Bypass 

mode

When input voltage is 

within acceptable range 

but UPS is overload, UPS 

will enter bypass mode 

or bypass mode can be 

set by front panel. Alarm 

is sounding every 10 

seconds.

Engli

sh

Română

Summary of Contents for Balder 1500

Page 1: ...Balder Series User Manual Manual de utilizare PWUP OL150BA AZ01B PWUP OL300BA AZ01B v 1 Before using this product carefully read all product documentation and retain it for future reference...

Page 2: ...alderSeries Balder 1500 Balder 3000 1500VA 3000VA Thank you for purchasing our products Please read this manual before using the product Focusing on quality at competitive prices nJoy designs consumer...

Page 3: ...r 3000 U S B E P O O U T R S 2 3 2 I N N E T W O R K F A X M O D E M I N T E L L I G E N T S L O T P R O G R A M M A B L E O U T L E T S P 1 O U T P U T I N P U T 1 0 A m a x English Rom n USB EPO OUT...

Page 4: ...luids or other foreign objects from entering the inside of the UPS system Maintenance service and faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified ma...

Page 5: ...ect battery wires please follow below steps Step 2 Connect to External Battery Pack When connecting external battery packs please be sure to connect polarity correctly Connect positive pole of battery...

Page 6: ...ical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices DoNOTplugLASER PRINTERSintoanyof the...

Page 7: ...o connect RS 232 USB port of UPS and RS 232 USB port of PC Install the UPS monitoring software from https www power software download com viewpower html to fully configure UPS shutdown Operations 5 Bu...

Page 8: ...nute S second Configuration and fault information 88 SET Indicates the configuration items and the con figuration items are listed in details in section 5 5 88 FAULT CODE Indicates the warning and fau...

Page 9: ...Indicators 5 3 LCD display wordings index 5 4 Mode Alarm Battery Mode Sounding every 5 seconds Low Battery Sounding every 2 seconds Overload Sounding every second Fault Continuously sounding Bypass Mo...

Page 10: ...e settings options or values for each program Interface Settings 01 Output voltage settings Parameter 2 Output voltage 200 presents output voltage is 200Vac 208 present output voltage is 208Vac 220 pr...

Page 11: ...le or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range setting Parameter2 Set theacceptable high voltagepoint andac...

Page 12: ...ng current based on battery capacity used Please use the following table as reference Battery capacity AH Total charging current A 7 20 2 20 40 4 40 60 6 60 80 8 80 100 10 100 150 12 NOTE If you conne...

Page 13: ...in parameter 2 Default 110Vac 00 Exit setting Exit the setting mode Operating Mode Description 5 6 Operating mode Description LCD display Online mode When the input voltage is within acceptable range...

Page 14: ...ashing Code Alarm Low Battery bL Sounding every 2 seconds Overload OL Sounding every second Over input current OI Sounding 2 beep every 10 seconds Battery is not connected NC Sounding every 2 seconds...

Page 15: ...gs cautions and notes before replacing the batteries CAUTION Step 1 Remove front panel Step 2 Disconnect battery wires Step3 Pull out the battery box by removing the two screws on the front panel Step...

Page 16: ...battery terminals by following below chart Battery kit assemly procedure 6 1 Balder 1500 Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assemble...

Page 17: ...service unit Problem Possible Cause Solutions Fault code is shown as 28 on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact service unit The ic...

Page 18: ...12 13 and 41 on LCD display and alarm is continuously sounding A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 Th...

Page 19: ...00 3000 Mul umim pentru c a i ales produsele noastre V rug m citi i cu aten ie manualul de utilizare nainte de a pune n func iune acest produs Concetr ndu ne pe calitate la pre uri competitive constru...

Page 20: ...e urgen 9 Conector pentru cabinetul de baterii Balder 1500 U S B E P O O U T R S 2 3 2 I N N E T W O R K F A X M O D E M I N T E L L I G E N T S L O T P R O G R A M M A B L E O U T L E T S P 1 O U T P...

Page 21: ...ntru a deconecta sursa de alimentare Nu l sa i s ajung n interiorul unit ii UPS niciun obiect str in sau lichide ntre inere Service i Defecte Sistemul UPS func ioneaz cu tensiuni periculoase Repara ii...

Page 22: ...ta aceste cabluri v rug m s urma i pa i de mai jos Pasul 2 Conectare cabinet de baterii extern Atunci c nd conecta i UPS ul la un cabinet de baterii extern asigura i v c polaritatea este corect polul...

Page 23: ...i de curent pute i extinde timpul de backup la dispozitivele critice set nduntimpmaiscurtdebackuppentrudispozitivele non critice NU conecta i imprimante laser la nici una din prizele UPS ului NU conec...

Page 24: ...utoane 5 1 Butonul ON Mute Pornirea UPS ului Ap sa i i ine i ap sat butonul ON Mute pentru cel pu in 2 secunde pentru a porni UPS ul Oprirea alarmei C nd UPS ul este n modul de baterie ine i ap sat ac...

Page 25: ...Indic baterie func ional Indic faptul c UPS ul se ncarc de la re ea BYPASS Indic faptul c circuitul bypass func ioneaz ECO Indic faptul c Modul ECO e activat Indic faptul c circuitul AC DC func ioneaz...

Page 26: ...at DIS d15 Dezactivat ESC ESC Renun HLS HLS Prag superior LLS LLS Prag inferior AO AO Deschidere activ AC AC nchidere activ EAT EAt Autonomie r mas estimativ RAT rAt Autonomie acumulat SD Sd nchidere...

Page 27: ...nstabil EE EE Eroare EEPROM BR bR nlocuie te bateriile Interfa Set ri 01 Set ri tensiune la ie ire Parametrul 2 Tensiune la ie ire 200 tensiunea de ie ire este 200Vac 208 tensiunea de ie ire este 208V...

Page 28: ...az sau deactiveaz func ia de bypass Pute i alege una din urm toarele op iuni ENA Activare bypass DIS Dezactivare bypass implicit 07 Set rile plajei tensiunii de bypass Parametrul2 Stabili i valoareama...

Page 29: ...u valoarea maxim a curentului de nc rcare Dac folosi i cabinete de baterii externe v rug m s seta i valoarea maxim a curentului de nc rcare conform cu tabelul de mai jos Capacitate baterie AH Curent d...

Page 30: ...itele acceptate dar UPS ul este supra nc rcat va intra in Modul Bypass automat Alarma va suna o dat la fiecare 10 secunde 17 Conectarea unui transformator de izolare extern Parametru 2 Permite sau nu...

Page 31: ...re 2 secunde Frecven de bypass instabil FU Sun la fiecare 2 secunde nlocuire baterie br Sun la fiecare 2 secunde Eroare EEPROM EE Sun la fiecare 2 secunde Eroare Cod Icoan Eroare pornire BUS 01 Suprat...

Page 32: ...e nainte de nlocuirea bateriilor ATEN IE Pasul 1 nl tura i panoul frontal Pasul2 Deconecta icablurilebateriei Pasul 3 Scoate i cutia bateriei prin eliminarea celor 2 uruburi de pe panoul frontal Pasul...

Page 33: ...ta i toate bornele bateriei urm rind grafica de mai jos Procedura de asamblare a kit ului de baterii 6 1 Balder 1500 Pasul 1 ndep rta i benzile adezive Pasul 2 Conecta i toate bornele bateriei urm rin...

Page 34: ...Cauz posibil Solu ie Codul de eroare 28 p lp ie pe ecranul LCD i alarma sun continuu Tensiunea bateriei este prea mic sau nc rc torul este defect Contacta i unitatea de service Icoanele i iar codul d...

Page 35: ...blem Cauz posibil Solu ie Codul de eroare este afi at ca 01 02 03 04 11 12 13 sau 41 pe panoul LCD i alarma sun continuu O eroare intern a avut loc Exist dou posible rezultate 1 Sarcina este nc furniz...

Page 36: ...oned product was found in compliance with 2004 108 EC EMC Directive Also tested with the listed standards the above mentioned product was found in compliance with 2006 95 EC LVD Directive EN 62040 2 2...

Page 37: ......

Reviews: