18
19
Parameter 1
Parameter 2
BL
b L
Battery Low
OL
O L
Over Load
OI
O I
Over input current
NC
N C
Battery No Connect
OC
O C
Over Charge
SF
S F
Site wiring fault
EP
E P
EPO
TP
t
P
Temperature
CH
C H
Charger
BF
b F
Battery Fault
BV
b v
Bypass Out Range
FU
F U
Bypass frequency
unstable
EE
E E
EEPROM error
BR
b R
Battery
Replacement
UPS Settings
5.5
1
2
There are two parameters to set up the UPS.
•
Parameter 1:
For program alternatives. Refer to the table below.
•
Parameter 2:
The settings options or values for each program.
Interface
Settings
01:
Output voltage settings
Parameter 2: Output voltage:
200:
presents output voltage is 200Vac
208:
present output voltage is 208Vac
220:
present output voltage is 220Vac
230:
present output voltage is 230Vac
240:
present output voltage is 240Vac
NOTE: Derate capacity to 80% when
the output voltage is adjusted to
200VAC/208VAC.
02:
Frequency Converter enable/disable
Parameter 2: Enable or disable converter
mode.
You may choose the following two op-
tions:
CF ENA
: converter mode enable
CF DIS:
converter mode disable (Default)
NOTE: Derate capacity to 80% when
Frequency Converter mode is enabled.
Engli
sh
Română
Summary of Contents for Balder 1500
Page 37: ......