Diagnosis
page 117
rev. 00 / 12.04.2017
34 Simulation
This menu can be used to simulate theoretical flow. Simulation is executed by specifying
assumed values for levels and velocities. These values are not available in reality, however.
Using this simulated values the transmitter calculates the prevailing flow rate based on the
dimensions of the programmed channel.
This value is issued on the analog or digital outputs determined before.
Fig. 34-1
Enter password
DANGER
Personal injury or property damage
The simulation of analog outputs shall be executed by trained electricians only. The respon-
sible expert personnel must have sound knowledge on the entire control procedures of the
according facility.
Prepare the simulation process carefully:
- Switch the following systems to manual operation.
- Disable actuating drives and similar or limit the according function.
It is absolutely necessary to have a safety person available!
Disregarding may lead to personal injury or damage your facility.
NIVUS herewith in advance refuse any responsibility for any possible damage to persons
or objects at any extent due to the extremely high risk of danger and unforeseeable conse-
quences in the event of incorrect or faulty simulation!
DANGER
Effects on plant sections
The simulation of NivuFlow outputs will directly affect any following plant sections without
any safety locking measures!
Simulations are allowed to be executed exclusively by qualified expert personnel. Observe
the hints contained within the above warning!
Note
Due to the reasons of safety mentioned before the simulation mode access is pass-
word-protected.
Due to reasons of personal safety share your password only with authorised and
trained expert personnel!