P12: dcba Displayed process values and their units
FACTORY DEFAULT: 0100
The columns of the chart below can be programmed separately and it is supposed to be done reasonably (i.e. to have symbol LEV lit:
2
should
be set under
b,
to have relevant unit lit (m/ft or cm/in)
2 or 3
should be set under
a
and setting 1 under
d
should be chosen if the required unit is
meter or centimetre. This also means that there is no engineering unit to set for FLOW (it can be displayed in %)
Settings in column ‘
a’
make engineering units lit on the frame (
c
should be set to 0)
Settings in column ‘
b’
make the symbols (
DIST
,
LEV
,
VOL
,
FLOW
)
lit on the frame
Settings in column ‘
c’
make
%, mA or °C
lit on the frame (
a
should be set 0)
a
b
c
d
1
m
3
/ft
3
DIST %
M
2
m/ft LEV mA US
3
cm/in VOL
C
-
4
l/gal FLOW -
-
5
t - - -
6
F
- - -
P13: 00ba HART short address (for 3-wire models only)
FACTORY DEFAULT: 00
The short address of the unit for the multidrop system (HART network) is to be given here.
Please note that in accordance with the HART standards the address of a single device should be 00. In this case current output will change
according to the settings in the range of 3.8 – 22 mA and HART communication is also available.
For systems with more than one device 01 – 15 addresses should be given. In these cases the output current will be fixed to 4 mA. Thus,
information is transferred by the HART communication only (i.e. current output does not carry any information and error indication on the current
output is not possible). (See also ‘Description of EView2’ supplied with HART capable devices.)
P14: dcba Product version
Hardware and software versions of the model can be found in this parameter.
d = 0 not HART capable d = 1 HART capable c = hardware version, ba = software version