5.7 ALARM OUTPUT
There are three alarms that operate separately. In addition, the combined alarm operation and alarm option can
be set. Use the digital input setting as
[AlRE]
or turn off the unit and restart the unit to clear the alarm operation.
5.7.1 Alarm Operation
[PAR4 → AL-1]
Select the alarm operation. Default setting is “
DV
[[”
Mode Name
Alarm operation
Description (default)
OFF
-
-
No alarm output
DV]]
Deviation
upper limit
alarm
OFF
SV
100 °C
PV
110 °C
ON
H
Upper deviation:
Set to 10 °C
OFF
PV
90 °C
SV
100 °C
ON
H
Upper deviation:
Set to –10 °C
If the deviation between
PV
and
SV
is higher than
the set value for the high
temperature deviation, the
alarm output will turn on.
The upper limit deviation
temperature can be set
at
AL1H.
]]DV
Deviation lower
limit alarm
ON
OFF
PV
90 °C
SV
100 °C
H
Lower deviation:
Set to 10 °C
ON
OFF
SV
100 °C
PV
110 °C
H
Lower deviation:
Set to –10 °C
If the deviation between
PV
and
SV
is higher than
the deviation temperature
setpoint as a lower limit, the
alarm output will turn on.
The lower limit can be set
for the
AL1L
.
]DV[
Deviation
upper / lower
limit alarm
ON
ON
OFF
PV
120 °C
PV
90 °C
SV
100 °C
H
H
Lower deviation: Set to 10 °C
Upper deviation: Set to 20 °C
If the deviation of the upper
/ lower limit between
PV
and
SV
is higher than the
deviation temperature
setpoint, the alarm output
will turn on.
The upper limit deviation
temperature can be set
in
AL1H
.
The lower limit deviation
temperature can be set
in
AL1L
.
[DV]
Reverse alarm
upper / lower
limit
OFF
OFF
ON
PV
120 °C
PV
90 °C
SV
100 °C
H
H
Lower deviation: set to 10 °C
Upper deviation: set to 20 °C
If the difference between
the
PV
and
SV
upper / lower
limit is higher than the set
temperature difference, the
alarm output will turn off.
The upper limit deviation
can be set in
AL1H
.
The lower limit deviation
can be set in the
AL1L
.