9)  Declared performances:

  

Paragraph

Essential characteristics 

Performance-grade  EN 1125

Category of use 

3 - high frequency 

7.1

Durability 

7 - 200.000 cycles 

7.2

Door mass 

7 - over 200kg 

7.3

Suitability for use on fire/smoke doors  B - suitable 

7.4

Safety toward people 

1 - for escape routes  7.5

Corrosion resistance 

3 - 96 h (high resist.)  7.6

Security toward goods 

2 - 1000N 

7.7

Projection of horizontal bar 

1 - up to 150mm 

7.8

Type of horizontal bar operation 

A - push-bar 

7.9

Field of door application 

A - 1 or 2 leaved door  7.10

Dangerous substances 

conform 

ZA

10) Panic bars listed in point 1 and 2 are conform to the performances 

declared in point 9. This declaration of performance is issued under the 

exclusive responsibility of the manufacturer listed in point 4.

Signed in the name and on behalf of the manufacturer:

Ninz Karl

legal representative of the NINZ S.p.A.

RECOMMENDATIONS

In order to ensure that the panic bar could provide a high level of safety toward 

people and appropriate safety level toward goods, it should only be mounted 

onto doors and doorframes that are in good conditions. The door itself, 

therefore, should be checked to ensure that it was installed properly and that 

nothing obstructs its normal movement.

If rebate sealing are mounted on the door, make sure they do not inhibit proper 

functioning of the panic bar.

In case of two-leaved door where both leaves are equipped with panic 

bar, it is mandatory to check that each leaf opens when its respective 

panic bar is activated, and that leaves open freely when the bars are 

activated simultaneously.

The fastening instructions in the present document should be followed 

scrupulously during installation. Once installation is complete, the installer 

should give this document to the owner of the activity.

The horizontal bar should be installed in a way that maximizes its useable 

length.

For securing the door in the closed position, do not employ any other latching 

devices than those specified in the present document. This does not preclude 

the installation of automatic closing devices.

Different  external  access  devices  than  those  found  on  the  list  of  certified 

components on pages 4/4 are considered unacceptable.

The EXUS panic bar is also designed for installation on hollow metal doors with 

an internal cell structure.

If a door closer is needed to return the door to the closed position, care should 

be taken not to make the opening step more difficult for children, the elderly 

and the disabled.

A pictogram (arrow) should be positioned immediately above the horizontal bar 

on the internal side of the door.

All of the included components described herein must be positioned 

and mounted in conformity with the present document.

1) Identification code:

EXUS LA PANIC EXIT DEVICE

2) Identification number: 4204301.046 

KIT EXUS LA BMC

3) Intended product use: Panic exit device for escape routes suitable for one-

leaved doors or for the active leaf of two-leaved 

doors with dimensions up to 1350x2880mm/leaf, 

mass up to 300kg/leaf, mounted on hinges or 

pivots, with fire resistance up to EI

2

120 - REI120 

and smoke proof. Projection of the bar 125mm.

4) Manufacturer:

NINZ S.p.A. - corso Trento 2/A

I-38061 ALA (TN) 

www.ninz.it

tel. +39 0464 678300 - fax +39 0464 679025

5) Auth. representative: -

6) Assessment perf. sys.: system 1

7) Harmonized standard: EN 1125:2008 + EC1:2009

8) Notified body:

ICIM S.p.A. N.B. no. 0425 have issued the 

certificate of conformity for the factory production 

control no. 0425 CPR 001228.

SYMBOLS EMPLOYED

CAUTION

Indicates a danger that threatens people and/or material goods. Failure 

to observe the warnings indicated by this symbol may have serious 

consequences, such as personal injury and property damage.

ATTENTION

Indicates a danger that threatens material goods. Failure to observe 

the warnings indicated by this symbol may result in damage to material 

goods.

NOTICE

Warnings related to important technical aspects.

PRODUCT DESCRIPTION

Panic bar for one-leaved doors or for the active leaf of two-leaved doors located 

at emergency exits and activated by push-bars. Composed of galvanized 

steel controls, chrome-plated polished aluminium casing and lever, horizontal 

aluminium bar, stainless steel external lever handle with galvanized steel 

installation plate and panic safe lock.

OPERATION MODE

From the pull-side (handle side) the door can be opened at any time whereas 

from the push-side opening is always possible by using the horizontal bar of the 

EXUS LA BMC panic exit device.

WARNINGS

The EXUS panic bar activated by means of a horizontal bar is intended for use 

onto doors installed in escape routes where panic situations could develop.

The safety features of this product are of fundamental importance to ensure 

its conformity with EN 1125. It is strictly forbidden to introduce any type of 

modifications apart from those described in these installation instructions.

INSTALLATION, USE AND MAINTENANCE HANDBOOK