MANUAL  FOR  PHOTOELECTRIC  SMOKE  DETECTOR 

PRODUCT INTRODUCTION

 

This  product  named  Photoelectric  smoke  detector  (hereinafter 
called  detector)  detects  the  smoke  by  a  couple  of  infrared  diodes. 
The  principle  of  detecting  is  granule  in  the  smoke  can  reflect 
infrared  light.  Infrared  diodes  are  placed  in  the  special  chamber. 
The chamber can shield external light, but doesn’t affect the smoke 
into  it.  While  there  is  no  smoke,  the  diode  can  receive  very  weak 
infrared  light.  When  the  smoke  entering  the  chamber,  diode  can 
receive  more  and  more  light,  and  the  detector  can  give  out  alarm 
signal  when  the  smoke  attains  the  certain  density.  In  order  to   
reduce the interference  and lower power consumption, the  emitting 
circuit  adopts  the  pulse  signal.  The  product  in  accordance  with  the 
networking  approach  is  divided  into  2-wire  and  4-wire  detectors. 

PRODUCT FEATURE

   

● 

STRONG ADAPT ABILITY FOR CIRCUMSTANCE 

● 

SMT DESIGN, HIGH STABILITY 

● 

9-35VDC WIDE VOLTAGE         

● 

METAL SHIELD, ANTI-RFI & ANTI-EMI 

● 

LOW STANDBY CURRENT

 

 

POWER SUPPLY NON-POLARIZED INPUT 

 

FLASHING LED POWER INDICATOR   

 

ALARM RELAY N.C./N.O.OPTIONAL (4 WIRE) 

 

REMOTE LED INDICATOR OUTPUT (2 WIRE) 

TECHNICAL SPECIFICATION 

PRODUCT CATEGORY 

2 WIRE 

4 WIRE 

OPERATING VOLTAGE 

DC 9V~35V 

STANDBY CURRENT 

55uA 

100 uA (relay NO) 

12 mA (relay NC)

 

ALARM CURRENT 

20-25 mA @12V 

40-50 mA @24V

 

12-16 mA(relay NO) 

3-5 mA (relay NC)

 

ALARM INDICATION 

RED LED ON 

TEMPERATURE RANGE 

-10

~+50

℃ 

HUMIDITY 

0%~95%RH (NO CONDENSATION) 

ALARM OUTPUT 

REMOTE LED 

RELAY OUTPUT 

CONTACT RATING 

N/A 

0.5A@DC28V 

SENSITIVITY 

0.15dB/m (

+/-

0.03dB/m) 

STANDARD 

EN54-7,UL268 

DIMENSION 

100mm diameter*46mm deep 