MANUAL FOR PHOTOELECTRIC SMOKE DETECTOR
PRODUCT INTRODUCTION
This product named Photoelectric smoke detector (hereinafter
called detector) detects the smoke by a couple of infrared diodes.
The principle of detecting is granule in the smoke can reflect
infrared light. Infrared diodes are placed in the special chamber.
The chamber can shield external light, but doesn’t affect the smoke
into it. While there is no smoke, the diode can receive very weak
infrared light. When the smoke entering the chamber, diode can
receive more and more light, and the detector can give out alarm
signal when the smoke attains the certain density. In order to
reduce the interference and lower power consumption, the emitting
circuit adopts the pulse signal. The product in accordance with the
networking approach is divided into 2-wire and 4-wire detectors.
PRODUCT FEATURE
●
STRONG ADAPT ABILITY FOR CIRCUMSTANCE
●
SMT DESIGN, HIGH STABILITY
●
9-35VDC WIDE VOLTAGE
●
METAL SHIELD, ANTI-RFI & ANTI-EMI
●
LOW STANDBY CURRENT
●
POWER SUPPLY NON-POLARIZED INPUT
●
FLASHING LED POWER INDICATOR
●
ALARM RELAY N.C./N.O.OPTIONAL (4 WIRE)
●
REMOTE LED INDICATOR OUTPUT (2 WIRE)
TECHNICAL SPECIFICATION
PRODUCT CATEGORY
2 WIRE
4 WIRE
OPERATING VOLTAGE
DC 9V~35V
STANDBY CURRENT
55uA
100 uA (relay NO)
12 mA (relay NC)
ALARM CURRENT
20-25 mA @12V
40-50 mA @24V
12-16 mA(relay NO)
3-5 mA (relay NC)
ALARM INDICATION
RED LED ON
TEMPERATURE RANGE
-10
℃
~+50
℃
HUMIDITY
0%~95%RH (NO CONDENSATION)
ALARM OUTPUT
REMOTE LED
RELAY OUTPUT
CONTACT RATING
N/A
0.5A@DC28V
SENSITIVITY
0.15dB/m (
+/-
0.03dB/m)
STANDARD
EN54-7,UL268
DIMENSION
100mm diameter*46mm deep