Water after-heating element
With a water after-heating element you can increase the supply air temperature to the
desired level. The unit can be delivered with an integral water after-heating element. It
comes complete with the necessary sensors.
The water after-heating element is controlled by a Danfoss Actuator, which comes
connected to the unit.
The unit can also control external after-heating elements.
Water trap with ball
To ensure that condensate water can drain freely, a water trap must be installed.
You should check regularly that there is water in the trap. The water trap may dry out
during late spring, summer and autumn, when no condensation is formed. If the water
trap dries out, air will be sucked into the unit and condensate water will not be able to
drain. This will cause water damage.
Nilan’s water trap contains a ball that ensures that no air is sucked into the unit and that
condensate water can drain freely.
Heating cable - external
Nilan offers an external heating cable for frost protection of the condensate drain of 3m
and 5m respectively. Used in cases where Nilan water trap with ball is mounted and where
it is not possible to use the integrated heating cable. The 10W heating cable is equipped
with a thermostat, so it only heats when frost protection is needed.
Heating cable - integrated
You can order a 3 m long self-regulating heating cable as frost protection of the condensate
drain. The heating cable is built into the unit from the factory, and approx. 1.5 meters of
heating cable out of the drain plug, which must be routed internally in the condensate
drain.
It is up to the installer to ensure that the condensation water can run frost-free for
drainage.
Vibration absorbers
Sylomer vibration absorbers to place under the unit ensure that the vibrations of the unit
against the underlying surface are damped effectively.
VTZ Compressor
VTZ is a frequency controlled compressor with stable and constant regulation. The
compressor regulates the operation according to the cooling or heating requirement. It will
therefore reach a high COP value, which means low energy consumption.
The VTZ compressor can be used with the CTS602i and the CTS6000 automations.
16