80
SI-INTERBUS User Guide
Issue Number: 1
a data channel will only use 32 bits if the source/target drive parameter is a 32-bit
parameter. If the source/target drive parameter is only 1, 8 or 16 bits wide 16 bits will be
used for that particular data channel.
14.14 Serial number LS
The SI-Interbus module serial number is a 10-digit decimal number loaded during
manufacture and cannot be changed.
This parameter contains the last 8 digits of the serial number. (See also Pr
MM.055
).
14.15 Cyclic mapping status
If the SI-Interbus operating status parameter (Pr
MM.006
) indicates -3, a mapping
configuration error has been detected. The reason for the error is indicated by the
SI-Interbus mapping status parameter, Pr
MM.049
. When a mapping error has been
corrected, reset the SI-Interbus by setting Pr
MM.032
to On.
The full list of mapping error codes can be found in the Diagnostics section
(see
).
14.16 Module status
If SI-Interbus detects an error during operation, it will force a trip in the drive, and write
the SI-Interbus error code into this parameter.
MM.035
Serial Number LS
Minimum
0
Maximum
99999999
Default
None
Units
None
Type
32 Bit Volatile
Update Rate
Power-up write
Display format
Lead Zero Pad
Decimal Places
0
Coding
RO, ND, NC, PT
MM.049
Cyclic Mapping Status
Minimum
0
Maximum
255
Default
None
Units
None
Type
8 Bit Volatile
Update Rate
Background write
Display format
None
Decimal Places
0
Coding
RO, ND, NC, PT, BU
If the mapping configuration size has changed (Pr
MM.005
Interbus Data Format
), then
the module reset is insufficient to fully initialise the Interbus network and after saving
parameters, the module must be power-cycled.
NOTE
NOTE
MM.050
Module Status
Minimum
0
Maximum
255
Default
None
Units
None
Type
8 Bit Volatile
Update Rate
Background write
Display format
None
Decimal Places
0
Coding
RO, ND, NC, PT, BU