MECHANICAL INSTALLATION
Powerdrive MD2SL Installation and maintenance
5077 - 2017.12 / b
en
2.3 - Cooling
~ 85% of the
POwERDRIVE MD2SL
losses is located in
the coolant circuit. The remaining 15% losses are linked to
thermal radiation. electrolytic capacitors and electronic board
losses. These losses need to be removed by air circulation in
the cabinet.
2.3.1 - Drive losses
Losses @ 40°C
Rating
Duty
Losses (kw)
2kHz
3kHz
4kHz
180T
Heavy duty
3.4
3.6
3.8
Normal duty
4.1
4.4
4.5
220T
Heavy duty
4.1
4.3
4.6
Normal duty
5.3
5.5
5.6
270T
Heavy duty
4.9
5.2
5.5
Normal duty
6.2
6.5
6.9
340T
Heavy duty
6.2
6.5
6.9
Normal duty
7.6
8.0
8.5
400T
Heavy duty
7.1
7.5
7.9
Normal duty
8.6
9.0
9.3
470T
Heavy duty
8.8
9.3
9.5
Normal duty
10.5
11.1
10.8
570T
Heavy duty
9.9
10.4
9.7
Normal duty
12.0
12.2
11.0
750T
Heavy duty
13.0
13.7
14.5
Normal duty
16.1
16.9
17.3
900T
Heavy duty
16.1
17.0
17.8
Normal duty
19.7
20.8
20.3
1100T
Heavy duty
18.1
19.1
18.2
Normal duty
22.5
22.9
20.7
1400T
Heavy duty
24.4
25.6
26.8
Normal duty
29.6
31.2
30.4
1700T
Heavy duty
27.2
28.6
27.3
Normal duty
33.7
34.4
31.0
340TH
Heavy duty
6.1
6.5
7.2
Normal duty
7.7
8.1
9.0
400TH
Heavy duty
7.6
8.0
8.9
Normal duty
9.4
9.9
11.0
500TH
Heavy duty
8.9
9.3
10.3
Normal duty
11.4
12.0
13.3
600TH
Heavy duty
11.1
11.7
12.9
Normal duty
13.2
13.9
14.9
Rating
Duty
Losses (kw)
2kHz
3kHz
4kHz
750TH
Heavy duty
14.0
14.7
16.3
Normal duty
17.7
18.6
20.7
900TH
Heavy duty
16.3
17.2
19.1
Normal duty
21.3
22.5
24.9
1200TH
Heavy duty
20.4
21.5
23.9
Normal duty
24.8
26.1
27.9
1500TH
Heavy duty
24.4
25.7
28.5
Normal duty
32.0
33.7
37.4
1800TH
Heavy duty
30.8
32.4
36.0
Normal duty
37.0
39.0
41.7
2.3.2 - Air cooling
The purpose of the fan located on the cabinet roof is to
maintain a constant temperature inside the cabinet and also
to cool the passive components and circuit boards.
Never obstruct the drive ventilation. Ensure that hot air is
not being recycled via the air inlets by leaving sufficient free
space above the
POwERDRIVE MD2SL
or providing a
means of evacuating the hot air expelled by the product. If
necessary. add a suction duct.
The air inlet filters must be cleaned and changed regularly.
Drive ventilation flow rates and noise levels :
Rating
Flow rate
(m
3
/h)
Noise level
(dBA)
180T to 570T
250
65
750T to 1100T
500
68
1400T & 1700T
750
71
340TH to 600TH
250
65
750TH to 1200TH
500
68
1500TH & 1800TH
750
71
After connecting the power. reposition the cable
bush plates at the bottom of the cabinet and fill any
gaps with expanding foam.