SM-Applications Modules & Motion Processors User Guide
Issue Number: 4
Defines the scheduling rate for the POS tasks to suit the application performance and
the resource needed to run the user DPL program. The following values are defined:
Set this parameter in order for the user DPL program to automatically run at power-on/
reset. If this is changed and the new setting needs to be used on power-up ensure that
a
drive
parameter save is performed.
Setting this parameter to 1 will cause the drive to trip when certain run-time errors occur
within the Second Processor user DPL program.
For more information, see section 11.1
When this parameter is 0, the module will be reset when a drive trip is cleared. When set
to 1 the module will be unaffected by a drive trip reset (i.e. continue running)
Pr 81.12
POS task scheduling rate
Access
RW
Range
0 to 6
Default
0
Update Rate
Initialization
Display
Value
Description
diSAbled
0
Disabled
0.25
1
250
µ
s
0.5
2
500
µ
s
1
3
1ms
2
4
2ms
4
5
4ms
8
6
8ms
Apps
Apps Lite Apps Plus
Lite V2
ST Plus
ST Indexer
With the Unidrive SP version 01.03.00 and earlier, the display will not show the actual
rate, but its aliased number. For instance 250 µs will be shown on the display as 1.
Pr 81.13
Auto-run Enable
Access
RW
Range
0/1
Default
1
Update Rate
Initialization
Apps
Apps Lite Apps Plus
Lite V2
ST Plus
ST Indexer
Pr 81.14
Global Run-time Trip Enable
Access
RW
Range
0/1
Default
0
Update Rate
Initialization
Apps
Apps Lite Apps Plus
Lite V2
ST Plus
ST Indexer
Pr 81.15
Disable Reset on Trip Cleared
Access
RW
Range
0/1
Default
0
Update Rate
Initialization
Apps
Apps Lite Apps Plus
Lite V2
ST Plus
ST Indexer