Digistart D3: User Guide
47
Issue: G
6.2 Setup procedure
Action
Detail
Before power-up
Ensure:
•
The starter is not receiving a start signal
•
The motor is connected to the starter
•
The motor connection is correct
•
The correct supply voltage is available
Power up the starter
Ensure:
•
The Ready LED activates
Program parameters
The Quick Setup Menu makes it easy to configure the Digistart D3 for common
applications. The Digistart D3 selects the parameters relevant to the application and
suggests a typical setting, and you can adjust each parameter to suit your exact
requirements.
Press the
M
button.
To validate the Quick Setup Menu, press
M
again.
Select the application of your choice from the list.
The following applications are available through the Quick Setup Menu:
•
Pump (centrifugal, submersible)
•
Fan (damped, undamped)
•
Compressor (screw, reciprocating)
•
Conveyor
•
Crusher (rotary, jaw)
Use the
M
button to select the characteristics you want to modify and adjust the value
using and .
To confirm the selection, press the
M
key.
To exit the Quick Setup Menu and go back to the standard display, press
several
times.
For more information on the Quick Setup Menu, see
Quick setup details
.
For applications not covered by the Quick Setup Menu, select the Standard Menu,
then Menu 1 - Primary Motor Set and Menu 2 - Start/Stop Modes-1.
Press
M
to enter in the required menu.
The following parameters should be set to suit the requirements of the application:
•
1A
Motor Full Load Current
•
2A
Start Mode
•
2B
Current Limit
•
2D
Start Ramp Time
•
2I
Stop Time
•
2H
Stop Mode
(if required)
For parameter details, see
Parameter Descriptions
on page 65.
Start the motor
Ensure:
•
The status screen is shown on the starter display
•
The following terminals are closed: DI4, +24V, DI2, +24V and DI3, +24V
To start the motor, close terminal DI1, +24V.
To stop the motor, open terminal DI2, +24V.