Control - Heat pump EB101
S-SERIES – VVM S / SMO S
These settings are made on the display on the indoor mod-
ule/control module.
Menu 7.3.2 - Installed heat pump
Here, you make specific settings for the installed heat pump.
Silent mode permitted
Setting range: on/off
Max. frequency 1
Setting range: 25 – 120 Hz
Max. frequency 2
Setting range: 25 – 120 Hz
Compressor phase
Setting range S2125 1 x 230 V: L1, L2, L3
Detect compressor phase
Setting range S2125 1 x 230 V: off/on
Current limit
Setting range S2125 1 x 230 V: off/on
Max. current
Setting range S2125 1 x 230 V: 6 – 32 A
blockFreq 1
Setting range: on/off
From frequency
Setting range: 25 – 117 Hz
To frequency
Setting range: 28 – 120 Hz
blockFreq 2
Setting range: on/off
From frequency
Setting range: 25 – 117 Hz
To frequency
Setting range: 28 – 120 Hz
Defrosting
Start manual defrosting
Setting range: on/off
Start temperature for defrost function
Setting range: -3 – 3 °C
Cut-out value activation passive defrosting
Setting range: 2 – 10 °C
Defrost more often
Alternatives: Yes / No
Silent mode permitted: Here, you set whether silent mode
is to be activated for the heat pump. Please note that you
now have the option to schedule when silent mode will be
active.
The function should only be used for limited periods, because
S2125 possibly may not reach its dimensioned output.
Detect compressor phase: This shows in which the phase
the heat pump has detected whether you have S2125
230V~50Hz. Phase detection normally occurs automatically
in connection with start-up of the indoor module/control
module. This setting can be changed manually.
Current limitation: Here, you set whether the current limita-
tion function will be activated for the heat pump, if you have
S2125 230V~50Hz. During active function, you can limit the
value of the maximum current.
BlockFreq 1: Here, you can select a frequency range within
which the heat pump is not permitted to work. This function
can be used if certain compressor speeds cause noise dis-
turbance in the house.
BlockFreq 2: Here, you can select a frequency range within
which the heat pump is not permitted to work.
Defrosting: Here, you can change the settings that affect
the defrost function.
Start manual defrosting: Here, you can start "active defrost-
ing” manually, if the function needs to be tested for servicing
or if necessary. This can also be used to accelerate the start
of "fan de-icing".
Start temperature for defrost function: Here, you set the
temperature (BT16) at which the defrost function will start.
The value must only be changed in consultation with the
installer.
Cut-out value activation passive defrosting: Here, you set
the temperature (BT28) at which "passive defrosting" will
be activated. During passive defrosting, the ice is melted by
the energy from the ambient air. The fan is active during
passive defrosting. The value must only be changed in
consultation with the installer.
Defrost more often: Here, you activate whether defrosting
will occur more frequently than normal. This selection can
be made if the heat pump receives an alarm due to build-up
of ice during operation caused, for example, by snow.
NIBE S2125
Chapter 7 | Control
34
Summary of Contents for S2125