Nibe F2030 Installer Manual Download Page 5

Safety precautions

Caution

Install the system in full accordance with this installation
manual.

Incorrect installation can cause bursts, personal injury, water
leaks, refrigerant leaks, electric shocks and fire.

Observe the measurement values before working on the
cooling system, especially when installing in small rooms, so
that the limit for the refrigerant's density is not exceeded.

Consult an expert to interpret the measurement values. If the
refrigerant density exceeds the limit, lack of oxygen can occur in
the event of any leak, which can cause serious accidents.

Use original accessories and the stated components for the
installation.

If parts other than those stated by us are used, water leaks, electric
shocks, fire and personal injury may occur as the unit may not
work properly.

Ventilate the working area well – refrigerant leakage may
occur during service work.

If the refrigerant comes into contact with naked flames, poisonous
gas is created.

Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and
cause material damage and personal injury. Installation without
sufficient support can also cause vibrations and noise.

Ensure that the unit is stable when installed, so that it can
withstand earthquakes and strong winds.

Unsuitable installation locations can cause the unit to fall and
cause material damage and personal injury.

The electrical installation must be carried out by a qualified
electrician and the system must be connected as a separate
circuit.

Power supply with insufficient capacity and incorrect function
can cause electric shocks and fire.

Use the stated cables for the electrical connection, tighten
the cables securely in the terminal blocks and relieve the
wiring correctly to prevent overloading the terminal blocks.

Loose connections or cable mountings can cause abnormal heat
production or fire.

Check, after completed installation or service, that no refri-
gerant leaks from the system in gas form.

If refrigerant gas leaks into the house and comes into contact
with an aerotemp, an oven or other hot surface, poisonous gases
are produced.

Switch off the compressor before opening/breaching the
refrigerant circuit.

If the refrigerant circuit is breached /opened whilst the com-
pressor is running, air can enter the process circuit. This can cause
unusually high pressure in the process circuit, which can cause
bursts and personal injury.

Switch off the power supply in the event of a service or in-
spection.

If the power supply is not shut off, there is a risk of electric shocks
and damage due to the rotating fan.

Do not run the unit with removed panels or protection.

Touching rotating equipment, hot surfaces or high voltage parts
can cause personal injury due to entrapment, burns or electric
shocks.

Cut the power before starting electrical work.

Failure to cut the power can cause electric shocks, damage and
incorrect function of the equipment.

Care

Carry out the electrical installation with care.

Do not connect the ground lead to the gas line, water line,
lightning conductor or telephone line's ground lead. Incorrect
grounding can cause unit faults such as electric shocks due to
short-circuiting.

Use main switch with sufficient breaking capacity.

If the switch does not have sufficient breaking capacity, malfunc-
tions and fire can occur.

Always use a fuse with the correct rating in the locations
where fuses are to be used.

Connecting the unit with copper wire or other metal thread can
cause unit breakdown and fire.

Cables must be routed so that they are not damaged by
metal edges or trapped by panels.

Incorrect installation can cause electric shocks, heat generation
and fire.

Do not install the unit in close proximity to locations where
leakage of combustible gases can occur.

If leaking gases collect around the unit, fire may occur.

Do not install the unit where corrosive gas (for example ni-
trous fumes) or combustible gas or steam (for example
thinner and petroleum gases) can build up or collect, or where
volatile combustible substances are handled.

Corrosive gas can cause corrosion to the heat exchanger, breaks
in plastic parts etc. and combustible gas or steam can cause fire.

Do not use the unit where water splashes may occur, for ex-
ample in laundries.

The indoor section is not waterproof and electric shocks and fire
can therefore occur.

Do not use the unit for specialist purposes such as for storing
food, cooling precision instruments, freeze-conservation of
animals, plants or art.

This can damage the items.

Do not install and use the system close to equipment that
generates electromagnetic fields or high frequency harmon-
ics.

Equipment such as inverters, standby sets, medical high frequency
equipment and telecommunications equipment can affect the
unit and cause malfunctions and breakdowns. The unit can also
affect medical equipment and telecommunications equipment,
so that it functions incorrectly or not at all.

Do not install the outdoor unit in the locations stated below.

- Locations where leakage of combustible gas can occur.
- Locations where carbon fibre, metal powder or other powder
that can enter the air.
- Locations where substances that can affect the unit, for example,
sulphide gas, chlorine, acid or alkaline substances can occur.
- Locations with direct exposure to oil mist or steam.
- Vehicles and ships.
- Locations where machines that generate high frequency har-
monics are used.
- Locations where cosmetic or special sprays are often used.
- Locations that can be subjected to direct salty atmospheres. In
this case, the outdoor unit must be protected against direct in-
takes of salty air.
- Locations where large amounts of snow occur.
- Locations where the system is exposed to chimney smoke.

If the bottom frame of the outdoor section is corroded, or in
any other way damaged, due to long periods of operation,
it must not be used.

Using an old and damaged frame can cause the unit to fall and
cause personal injury.

If soldering near the unit, ensure that solder residue does
not damage the drip tray.

If solder residue enters the unit during soldering, small holes can
appear in the tray resulting in water leakage. To prevent damage,
keep the indoor unit in its packing or cover it.

Do not allow the drainage pipe to exit into channels where
poisonous gases, containing sulphides for example, can occur.

If the pipe exits into such a channel, any poisonous gases will
flow into the room and seriously affect the user's health and
safety.

Insulate the unit's connection pipes so that the ambient air
moisture does not condense on them.

Insufficient insulation can cause condensation, which can lead
to moisture damage on the roof, floor, furniture and valuable
personal property.

Do not install the outdoor unit in a location where insects
and small animals can inhabit.

3

Chapter 1 |

Important information

NIBE™ F2030

Summary of Contents for F2030

Page 1: ...Installer manual LEK NIBE F2030 Air water heat pump IHB GB 1540 4 231115...

Page 2: ......

Page 3: ...g and venting the heating medium sys tem 23 Balance temperature 23 Stop temperature 23 Soft starter 23 Compressor heater 23 Collar heater 23 Phase sequence control 24 Start up and inspection 24 Readju...

Page 4: ...ccordance to applicable parts of the machinery directive 2006 42 EC Children should be supervised to ensure that they do not play with the appli ance This is an original instruction manual Translation...

Page 5: ...ions and fire can occur Always use a fuse with the correct rating in the locations where fuses are to be used Connecting the unit with copper wire or other metal thread can cause unit breakdown and fi...

Page 6: ...r supply immediately after operation has start Wait at least 5 minutes otherwise there is a risk of water leakage or breakdown Do not control the system with the main switch This can cause fire or wat...

Page 7: ...llation data in the User manual Date Signature Notes Description System flushed System vented Particle filter Shut off and drain valve Charge flow set Fuses property Safety breaker Earth circuit break...

Page 8: ...e du Pou du Ciel 01600 Reyrieux FR Tel 04 74 00 92 92 Fax 04 74 00 42 00 E mail info nibe fr www nibe fr NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way Chesterfield S41 9QG GB Tel 0845 095...

Page 9: ...the neighbours F2030 must not be placed so that recirculation of the outdoor air can occur This causes lower output and impaired efficiency The evaporator should be sheltered from direct wind which n...

Page 10: ...s used to collect and lead away condensation water from the heat pump NOTE It is important to the heat pump function that condensation water is led away and that the drain for the condensation water r...

Page 11: ...arv Vattenl s LEK APH Water seal Joint The condensation water is lead to an indoor drain subject to local rules and regulations Route the pipe downward from F2030 The condensation water pipe must have...

Page 12: ...n avst nd vid anv ndning av flera F2030 600 mm 3000 mm 400 mm Minimalt fritt utrymme 600mm Minimalt fritt utrymme Minimum free space Free space behind Free space in front Minimum free space Minimum di...

Page 13: ...Removing the side cover LEK APH 11 Chapter 2 Delivery and handling NIBE F2030...

Page 14: ...1 EP2 BT17 BP2 AA101 QN1 QN31 WM5 QN30 QN34 GQ10 HS1 AA100 UB1 XL40 EB13 GQ1 EB11 QN2 XL20 EB10 BP10 RM1 APH BT16 EP1 UB1 XL40 PF3 XL2 BT3 XL1 BT12 BT28 PF1 PF3 NIBE F2030 Chapter 3 The heat pump desi...

Page 15: ...T16 Temperature sensor suction gas BT17 Temperature sensor ambient BT28 Electrical components Joint card sensor AA100 Joint card AA101 Compressor heater EB10 Condensation water trough heater EB11 Coll...

Page 16: ...3 Fan control board AA102 Phase sequence monitor 3 phase BA1 Fuse for external heating cable 250 mA F3 Automatic protection 10 A 30 mA FB1 Motor fuse FC2 Contactor main contactor fan QA51 Terminal blo...

Page 17: ...lower connection XL2 on F2030 All outdoor pipes must be thermally insulated with at least 19mm thick pipe insulation Install shutoff and drain valves so that F2030 can be emptied in the event of prolo...

Page 18: ...LiYY screened LiYCY Cable area at least 0 22with cable lengths less than 50m Alternatively the relevant screened signal cable is connected from terminal block X5 to the indoor module from NIBE The rou...

Page 19: ...Accessibility electrical connection Removing the side cover Unscrew the screws and lift off the cover LEK APH 17 Chapter 5 Electrical connections NIBE F2030...

Page 20: ...o high voltage cable when cable routing Power connection LEK APH Incoming supply Connection Incoming supply cable is supplied and factory connec ted to the terminal block X1 Approx 1 8 m cable is acce...

Page 21: ...mp To let F2030 control the charge pump GP12 connect it to the terminal block X3 1 PE 3 L and 4 N Pump activity is dependent on the status of F2030 heat ing hot water requirement and the ambient tempe...

Page 22: ...image 5 6 7 4 2 3 1 External F2030 X3 EB14 External heat cable F3 NOTE The pipe must be able to withstand the heat from the heating cable To ensure this function the accessory KVR 10 should be used C...

Page 23: ...included in this time If the ambient temperature falls to a level below the set value stop temperature downtime in channel A7 compressor operations are blocked and all heating must take place using th...

Page 24: ...ontact for external indication of common alarms The function becomes active with all types of existing alarms Max load on the relay con tact is250V 2A The connection for external indication of common...

Page 25: ...below the set value for stop temperature heating must occur using the addi tional heat Soft starter F2030 is equipped with a soft start AA10 that limits the inrush current for the compressor Compress...

Page 26: ...r 9 Restart any NIBE SMO or NIBE indoor module See information in relevant manual on www nibe eu 10 Once the connection is made the compressor starts after approx 180 minutes if needed 11 Adjust the c...

Page 27: ...rees lower Quoted outputs refer to compressor fan and control at nominal heating medium flow During operation that requires defrosting the relationship between input and output is reduced by about 10...

Page 28: ...can be adjusted and read off in the indoor module Navigation LP HP 34 15 88 90 86 41 33 89 93 34 91 Plus button The plus button S1 is used to browse through the channel system forwards or raise the v...

Page 29: ...lways active when the compressor is switched off The condensation water trough heater is connected during defrosting when the ambient temperature falls below or is equal to 2 5 C If the collar heater...

Page 30: ...at any point during the total 60 minutes falls below channel A7 2 1 C the counter is reset It does not start counting again un less the temperature is sufficiently high once again B Set temperature f...

Page 31: ...outdoor air 3 When the temperature on the return line sensor channel T3 falls below 10 C 4 The high pressure switch deploys during defrost ing This is indicated as alarm 10 in channel S1 and the comp...

Page 32: ...5 The temperature on the flow temperature sensor falls below 4 C NIBE F2030 Chapter 7 Control Introduction 30...

Page 33: ...within 240 minutes it becomes continuous Low evaporation temperature Appears if 10 safety defrosts in a row have occurred 19 Value S2 Shows the compressor status Compressor off 00 Compressor on 01 Com...

Page 34: ...heat is permitted The value is A6 adjustable between 1 and 120 minutes Factory setting 120 minutes Stop temperature the set outdoor air temperature value when the downtime relay is activated F2030 A7...

Page 35: ...ettings on the control equipment Fuses have tripped Replace the fuse or reset the MCB Cold outdoor air Indicated as 03 in channel S1 Wait until the ambient temperature is 2 C higher than the heat pump...

Page 36: ...ar heater in channel A14 Ice build up on the fan blades and front grille NOTE Only applies in certain areas Deicing fan channel A15 not activated Activate deicing fan in channel A15 Sensor placement B...

Page 37: ...87 4 348 45 1 426 3 583 50 1 278 2 968 55 1 136 2 467 60 1 007 2 068 65 0 891 1 739 70 0 785 1 469 75 0 691 1 246 80 0 607 1 061 85 0 533 0 908 90 0 469 0 779 95 0 414 0 672 100 Data for hot gas senso...

Page 38: ...3 25 3 82 15 13 20 3 58 11 88 15 3 33 9 392 10 3 07 7 481 5 2 80 6 000 0 2 54 4 844 5 2 28 3 935 10 2 03 3 217 15 1 80 2 644 20 1 59 2 186 25 1 39 1 817 30 1 22 1 518 35 1 07 1 274 40 0 93 1 075 45 0...

Page 39: ...0 With integrated EMK 310 Part no 069 084 VVM320 Copper 3 x 400 V Part no 069 108 Stainless Steel 3 x 400 V Part no 069 109 Enamel 3 x 400 V With integrated EMK 300 Part no 069 110 Stainless Steel 3 x...

Page 40: ...G1 28 mm Connection heating medium in to F2030 XL2 40 mm Connection drip tray drain XL40 400 mm Fritt utrymme bakom Fritt utrymme framf r Min avst nd vid anv ndning av flera F2030 600 mm 3000 mm 400 m...

Page 41: ...bricks differences in ground level etc and should therefore only be seen as guide values F2030 works with low fan speed or high fan speed depending on the ambient temperature 2 m 6 m 10 m 9 7 51 58 5...

Page 42: ...50 Hz Rated voltage 8 8 6 8 Arms Max operating current heat pump 6 3 4 3 Arms Max operating current compressor 23 5 19 2 Arms Starting current 41 68 48 68 W Nominal output fan low high 10 10 Arms Fus...

Page 43: ...te Europe 3 3 9 5 3 3 7 SCOP 55 Average climate Europe 3 6 7 5 3 6 5 5 SCOP 35 Cold climate 3 1 8 3 1 6 SCOP 55 Cold climate 4 5 10 4 6 7 5 SCOP 35 Warm climate 3 9 11 5 3 9 8 5 SCOP 55 Warm climate 1...

Page 44: ...temperature C C Outdoor air temperature 0 10 20 30 40 50 60 70 20 30 10 0 10 20 30 0 10 20 30 40 50 60 70 20 30 10 0 10 20 30 Supply temperature Return temp During shorter time it is allowed to have l...

Page 45: ...ual energy consumption space heating warm cli mate 1 577 1 572 kWh Annual energy consumption water heating warm climate 142 120 142 122 Seasonal space heating energy efficiency cold climate 88 87 Wate...

Page 46: ...COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air temperature C 4 Tbiv Bivalent temperature COPcyc Cycling interval efficiency kW Pcych Cycling interval capacity C 65 WTOL M...

Page 47: ...if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air temperature C 5 1 Tbiv Bivalent temperature COPcyc Cycling interval efficiency kW Pcych Cycling interval capacity C 65 WTOL Max supply...

Page 48: ...Electrical circuit diagram NIBE F2030 Chapter 11 Technical data 46...

Page 49: ...47 Chapter 11 Technical data NIBE F2030...

Page 50: ...NIBE F2030 Chapter 11 Technical data 48...

Page 51: ...49 Chapter 11 Technical data NIBE F2030...

Page 52: ...33 E Electrical cabinet 14 Electrical circuit diagram 46 Electrical connections 16 Charge pump 19 Connecting accessories 22 Connections 18 General 16 Optional connections 21 Power connection 18 Energ...

Page 53: ...hnical Data 40 Technical Data 40 Temperature channels 31 The heat pump design 12 Component list electrical cabinet 14 Component location electrical cabinet 14 Component locations 12 List of components...

Page 54: ......

Page 55: ...ns Do not dispose of used products with normal household waste It must be disposed of at a special waste station or dealer who provides this type of service Improper disposal of the product by the use...

Page 56: ...WS name Gemensamt WS version a74 working edition Publish date 2015 08 31 08 25 231115 NIBE AB Sweden Hannabadsv gen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu...

Reviews: