If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Caution
Also see the Operating Manual for false.
Start guide
The start guide appears at first start-up after installation,
but is also available in menu 5.7.
Menu system
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 1.1.1 - heating
Make settings for room temperature here.
Menu 1.9.1.1 - heating curve
Make settings for your own heating curve here.
Menu 3.1 - service info
Here you will find temperatures and other operating in-
formation for GreenMaster-HP.
Menu 5.1.7 - br pmp al set.
Make settings for the brine alarm in GreenMaster-HP
here.
Menu 5.1.9 - brine pump speed
Set the speed of the brine pump in GreenMaster-HP
here.
Menu 5.1.11 - pump speed heating medium
Set the speed of the heating medium pump in GreenMas-
ter-HP here.
Menu 5.1.14 - flow set. climate system
Make settings for the flow in the climate system here.
Menu 5.2.4 - accessories
Activate the air treatment unit here.
Activate: GreenMaster-HP
Menu 5.3.22 - greenmaster C-F
Make operating settings for GreenMaster-HP in this
menu.
start manual motion QM41
yes/no
QM41 motion interval
Set the interval in days for how often the fire damper
(QM41) is to be actuated here.
Setting range: 1–30
Default value: 14
set point value
Make settings for the control’s set point value here.
Setting range: 0–400 Pa
Factory setting: 150 Pa
min. fan speed GQ2
Setting range: 1–99%
Factory setting: 10%
TIP
If both settings are set to the same value, the
fan operates at fixed speed.
max. fan speed GQ2
Setting range: 2–100%
Factory setting: 100%
months btwn filter alarms
Set the number of months between filter changes in
GreenMaster-HP here.
Setting range: 1–24
Factory setting: 12
runtime damper QM41
Make settings for the max. actuating time before an
alarm triggers here. Set the max. actuating time before
an alarm is activated here.
Setting range: 1–300 s
Factory setting: 150 s
outd temp compensation
-55
-20
-15
-10
-5
0
5
10
15
20
25
-45
-35
-25
-15
-5
5
Kompensering
(Pa)
Utetemperatur
(°C)
Compensation
(Pa)
Outdoor temperature
(°C)
Setting range: -100–0 Pa
Default value: 0
type of fire alarm
Make settings for the fire alarm in GreenMaster-HP here.
Setting range: 1/2
Default value: 1
35
Chapter 7 |
Control - menus
GreenMaster-HP
7 Control - menus