Commissioning
42
TemBreak
PRO
B_BE-UM-001-EN
– V1.1.0
LSIG 3P
–
GF Protection Adjustments (I
g
)
On the LSIG 3P variant B_BE MCCB, the GF protection is configured by the GF DIP switch, which is used to enable or disable GF protection, and is
performed as follows. Refer to
Ground/Earth Fault Protection (GF)
section for further detail on GF protection.
Action
Note / Illustration
1
Turn the MCCB to the OFF Position
Open the transparent flap in order to access the GF DIP
switch.
2
Move the GF dip switch using a small flat head screwdriver.
Position the DIP switch to ON or OFF.
Summary of Contents for TemBreak PRO
Page 45: ...45 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex A Dimensions B250P ...
Page 46: ...Annex A Dimensions B250 46 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 47: ...Annex A Dimensions 47 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 48: ...Annex A Dimensions B400P R 48 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 49: ...Annex A Dimensions 49 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 50: ...Annex A Dimensions B800N H G 50 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 51: ...Annex A Dimensions 51 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 52: ...Annex A Dimensions B800P R 52 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 53: ...Annex A Dimensions 53 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 54: ...Annex A Dimensions B1000N H 54 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 55: ...Annex A Dimensions 55 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 56: ...Annex A Dimensions B1250N H HL 56 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 57: ...Annex A Dimensions 57 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...
Page 58: ...Annex A Dimensions B1600N HL 58 TemBreak PRO B_BE UM 001 EN V1 1 0 ...
Page 89: ...89 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex C I2t Let Through Curves B250P ...
Page 90: ...Annex C I2t Let Through Curves 90 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 91: ...Annex C I2t Let Through Curves 91 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 92: ...Annex C I2t Let Through Curves 92 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 93: ...Annex C I2t Let Through Curves 93 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 94: ...Annex C I2t Let Through Curves 94 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 95: ...Annex C I2t Let Through Curves 95 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...
Page 96: ...96 TemBreak PRO B_BE UM 001 EN V1 1 0 Annex D Peak Let through Curves B250P ...
Page 97: ...Annex D Peak Let through Curves 97 TemBreak PRO B_BE UM 001 EN V1 1 0 B400P R ...
Page 98: ...Annex D Peak Let through Curves 98 TemBreak PRO B_BE UM 001 EN V1 1 0 B800N H G ...
Page 99: ...Annex D Peak Let through Curves 99 TemBreak PRO B_BE UM 001 EN V1 1 0 B800P R ...
Page 100: ...Annex D Peak Let through Curves 100 TemBreak PRO B_BE UM 001 EN V1 1 0 B1000N H ...
Page 101: ...Annex D Peak Let through Curves 101 TemBreak PRO B_BE UM 001 EN V1 1 0 B1250N H HL ...
Page 102: ...Annex D Peak Let through Curves 102 TemBreak PRO B_BE UM 001 EN V1 1 0 B1600N HL ...