5.5
Condenser Sensor Alarms
The controller has detected an open circuit on the condenser input, please check:
`
The condenser sensor is properly connected to the condenser input on the controller
`
The condenser sensor is reading the correct temperature – Temperature versus resistance:
Thermistor is Negative Temperature Coefficient (NTC)
`
The condenser input on the controller is in working order – The controller should not register
a PF2 alarm when a known working condenser sensor is connected
5.6
Freeze-up protection (888)
Problems with freeze-up protection may occur if the ambient temperature falls below 0°C (32°F) or if the
appliance sensor fails.
The controller has detected a below nominal temperature for the cabinet, please check:
`
The appliance sensor is properly connected to the appliance input on the controller
`
The correct positioning of the appliance sensor
`
An adequate DTT parameter setting has been selected (when taking into account the cabinets
temperature settings)
`
The appliance sensor is reading the correct temperature – Temperature versus resistance:
Thermistor is Negative Temperature Coefficient (NTC)
`
The appliance input on the controller is in working order – The controller should register a PF1
alarm when the appliance sensor is not connected
5.7
Condenser high temperature (Ht) alarms
Condenser high temperature (Ht) alarms alert to problems with the refrigeration system such as a blocked
condenser or faulty condenser fan.
The controller has detected an above nominal temperature for the condenser, please check:
`
Adequate airflow through condenser – Condenser grill is free from obstructions
`
Condenser fan operation
`
Evaporator for excessive freeze up
`
An adequate HT parameter setting has been selected (when taking into account the ambient
temperature)
`
If there is Refrigeration System leakage