5 Menu tree
5.8 MAIN MENUE – Doors
FST-2_HB.EN12/05
139
5.8 MAIN MENUE – Doors
All menu items with adjustable values can be deactivated by entering the
value “0”.
Menu item
Description
Setting
Doors basic –
Number doors
Number of car doors.
0 .. 3
Doors basic –
Apply–ALL
The settings in
Doors selective
automatically apply to
all car doors.
YES
NO
Doors basic –
Cam delay
Delay between reaching the levelling position or the zone area
and dropping off of the lock-cam curve (retiring cam for
unlocking the shaft doors, FSM X6.5).
0 .. 4 sec
Doors basic –
Cam time Max
Maximum activation time of the retiring cam. Prevents the
solenoid from damage in case of failures. After this time has
elapsed, output FSM X6.5 for the retiring cam is switched off,
independent from the state of the controller.
0010 .. 9999 sec
Doors basic –
Lock delay
Maximum delay between closing of the car door contact and
the shaft door/locking contact when closing the doors. If this
time is exceeded, the error
DOOR LOCK TIMEOUT
is
displayed. The car door opens for the set
Retry time
and
then closes again.
0 .. 4 sec
Doors basic –
Lock fail Max
Maximum number of consecutive lock fails (
DOOR LOCK
TIMEOUT
). All landing and car calls will be deleted and the
error
DOOR LOCK RETRY CNT
is displayed if this number
is exceeded.
0 .. 10
Doors basic –
Lock fail open
Door allocation after lock fail:
One: Only the car door last opened opens after a lock fail
(
DOOR LOCK TIMEOUT
).
All: All car doors open after a lock fail (
DOOR LOCK
TIMEOUT
).
ONE
ALL
Doors basic –
SCCT debounce
Delay between closing of the safety circuit and activation of
the drive contactors when starting (prevents contactor
bouncing).
0 .. 2.5 sec
Doors basic –
Retry time
Opening time of the car door before closing again after a lock
fail (
DOOR LOCK TIMEOUT
).
0 .. 4 sec
Doors basic –
Open delay
Delay before opening the doors after the levelling position has
been reached (see “Door times diagram” on page 143).
0 .. 4 sec
Doors basic –
Bypass t–OFF
Delay when switching off the safety circuit bypass relay K20.
0 .. 2 sec
Doors basic –
Bypass t–ON
Delay when switching on the safety circuit bypass relay K20.
0.1 .. 2 sec
Doors Basic –
Pre-Opening
Enable approaching with car and shaft doors open. This
parameter can only be activated when using the A6 Safety
Circuit! The following steps are required to deactivate an
integrated A6 Safety Circuit:
-
Set
Pre-Opening = NO
-
Set
Relevelling = NO
-
Disconnect power supply of the safety circuit (terminal 518/
519)
YES
NO
Summary of Contents for FST-2
Page 6: ...Table of contents 4 FST 2_HB EN12 05...
Page 98: ...5 Menu tree 5 1 General 96 FST 2_HB EN12 05 Fig 5 1 FST 2 Controller menu tree part 1...
Page 99: ...5 Menu tree 5 1 General FST 2_HB EN12 05 97 Fig 5 2 FST 2 Controller menu tree part 2...
Page 100: ...5 Menu tree 5 1 General 98 FST 2_HB EN12 05 Fig 5 3 FST 2 Controller menu tree part 3...
Page 101: ...5 Menu tree 5 1 General FST 2_HB EN12 05 99 Fig 5 4 FST 2 Controller menu tree part 4...
Page 102: ...5 Menu tree 5 1 General 100 FST 2_HB EN12 05 Fig 5 5 FST 2 Controller menu tree part 5...
Page 103: ...5 Menu tree 5 1 General FST 2_HB EN12 05 101 Fig 5 6 FST 2 Controller menu tree part 6...
Page 104: ...5 Menu tree 5 1 General 102 FST 2_HB EN12 05 Fig 5 7 FST 2 Controller menu tree part 7...
Page 105: ...5 Menu tree 5 1 General FST 2_HB EN12 05 103 Fig 5 8 FST 2 Controller menu tree part 8...
Page 174: ...6 Programmable inputs and outputs 172 FST 2_HB EN12 05...