background image

MODEL # NSSF6-2 System Feeder
Installation, Operation and Maintenance Instructions

PIPING CONNECTIONS

 

1. Place the NSSF6-2 on a secure level

base or use the optional wall
mounting brackets

2. Using the appropriate pipe

or tubing, connect the outlet
of NSSF6-2 ball valve to the system
— do not use metallic fittings. Use
an approved thread sealant for PVC
and
do not over tighten. Be sure
to secure the ball valve while
tightening the fitting.

3. If possible, the NSSF6-2 should be

connected to the system
at the point of no pressure change
— where the expansion tank is
connected to the system. 

DO NOT

install a check valve,

 

pressure

reducing valve or a

 

back flow

preventer between

 

the NSSF6-2

and the system.

 If using a bladder

style expansion tank, be sure to
inflate the tank to the same
pressure as the cold static pressure
of the system. This should be done
with zero system pressure.

4. After piping connections between

the NSSF6-2 and the system have
been completed, the NSSF6-2 can
be been filled with fluid (water or
glycol up to 50% solution).

ELECTRICAL CONNECTIONS

1. Connect the power adapter
to

 the right side of the control box

mounted on the NSSF6-2. The
main body of the UL listed power
adapter has two hook and loop
strips on the back and these can
be used to mount the power
adapter to a convenient surface.

1.

The NSSF6-2 is factory set with a

 

16

PSI cut-out and a 15PSI cut-in.

 

DO

NOT SET CUT-OUT

 

PRESSURE

ABOVE 50 PSI.

2.

To adjust these settings, the
pressure switch should be in the
“Off” position (“Run” LED 

OFF

).

a.

Push “Set” 

button 

and the

“Down” LED

 

will come on. The

number will

 

flash. Use up and

down arrows

 

to set the cut in

pressure.

 

Press set to save the

desired

 

cut in pressure.

b.

After pressing the set button to
lock cut in pressure, the UP

 

LED

will come on and the

 

number

will again flash. Use up

 

and

down arrow

s

 to set cut out

pressure. 

DO NOT SET ABOVE

50 PSI.

 Press "set" button to

 

lock

in cut out pressure.

START-UP

1. Press the on off button and open

the ball valve. The pump will come
on and start pumping fluid into
the system. The “Run” LED will
flash while the pump is running
and will be solid when the pump
stops. The “UP” LED will light
when the system reaches pressure
and the pump stops. The “DOWN”
LED will light while the pump is
running.

2. The pump may cycle on and off

until the system pressure settles —
this is normal. Cycling may
continue until all of the air is
eliminated from the system.

3. If the fluid level in the tank

continues to drop for an undue
amount of time, check for leaks
and repair as needed.

FLOAT SWITCH

A dry alarm contact can be accessed 
through the blank connector on the 
left side of the control box. When the 
fluid level gets low, the float switch in 
the tank will shut the pump off and 
close the alarm contact (no/c/nc) on 
the circuit board. External alarm can 
have a maximum 1 amp load.

Replacement parts are available.

SETTING PRESSURE UNITS

The pressure switch is factory set to 
display “PSI”. To change this setting:

1. Press “Off”

2. Press “Up” to scroll through

pressure units.

3. Press “Set” to save setting.

ELECTRICAL CONNECTIONS

2. With the NSSF6-2 ball valve in

the off position, plug the AC end of
the power adapter into a standard
120 volt outlet.

PRESSURE SWITCH SETTINGS

The pressure switch includes a digital 
display, 4 buttons and 7 LEDs. 

When power is first applied to 
the NSSF6-2 it will default to standby 
— the green LED on the power 
adapter will light together with the 
following red LEDs on the pressure 
switch — Power, PSI and Run (“Run” 
will flash until system pressure 
matches Cut-out setting). The digital 
readout will also show a reading close 
to zero.

ADJUSTING CUT-OUT AND 
CUT-IN

Neutrasafe Corporation 

421 Page St., Ste. 1, 
Stoughton, MA 02072 
781-616-3951
www.neutrasafe.com

Reviews: