Network Technologies Incorporated ENVIROMUX-SDS-CELC Installation Instruction Download Page 1

 

 
 

ENVIROMUX-SDS-CELC(P) 

PHOTOELECTRIC SMOKE 

DETECTION SENSOR 

 

Installation Instruction 

 
 
 

Introduction 

 

The ENVIROMUX-SDS-CELC(P) is a smoke detection sensor intended for connection to an NTI ENVIROMUX-MICRO-T(RHP), 
ENVIROMUX-16D/5D/2D, or  ENVIROMUX-MINI-LXO (ENVIROMUX).    When properly connected, the ENVIROMUX-SDS-CELC(P) 
will provide signals to the ENVIROMUX that with proper configuration will result in alert messages being sent to users of the 
ENVIROMUX. The ENVIROMUX-SDS-CELC(P) has screw terminals for easy user connections and the ENVIROMUX-SDS-CELCP 
includes a 12VDC AC adapter.   
 
This Photoelectric smoke detector (hereinafter called Detector) detects smoke using a couple of infrared diodes. The principle of 
detecting is based on the fact that a granule of smoke can reflect infrared light.  Infrared diodes are placed in a special chamber. The 
chamber can shield external light, but doesn't prevent smoke from entering it.   In the absence of smoke, the diodes can detect very 
weak infrared light. As smoke enters the chamber, the diodes will receive more and more light.  When the smoke reaches a certain 
density, the Detector will sound out an alarm signal. In order to reduce interference and lower power consumption, the emitting circuit 
uses a pulse signal.  The Detector has a special structural design and ASIC, providing a dustproof, mothproof and anti-outside light 
interference feature.  The Detector is suitable for detecting the smoke in a house, shop, hotel, restaurant, office building, school, bank, 
library, etc. 
 

Product Features 

The detector works once connected directly to DC power. A flashing LED indicates the Detector is working normally and an LED that 
stays ON solid indicates an alarm condition.  Normally-closed output contacts will open in an alarm condition.   Connections to these 
contacts are made when the Detector is secured to the mounting base.  

 

Infrared Photoelectric Smoke Detector

 

 

LED alarm indicators

 

 

Selectable Alarm Output N/C or N/O Relay  (Default is N/C)

 

 

Selectable Latching Feature  (Default is latch ON)

 

 

Open Contact/LED Indicating Alarm

 

 

Anti-light, Mothproof, Dustproof

 

 

Stainless steel shield, Anti-RFI 

(20V/m-1GHz)

 

 
 

Preparation for Installation 

1. There should be no large objects that would block airflow within 0.5m (20 inches) of 

the Detector. 

2.

 

There must be no source of wind flow within 1.5m (60 inches) of the Detector. 

3.

 

The Detector should be mounted more than 0.5m (20 inches) from any wall.  

4.

 

The distance between two Detectors can be no less than 15m (50 feet) and the 

distance between Detector and corner must he less than half of the distance between 

Detectors. 

5.

 

Always install the Detector on a horizontal surface.   If it must be installed on a 

slanted surface, the angle of slant must be less than 45 degrees.  

6.

 

Clean the Detector by brushing the openings in the head with a soft brush every six months 

to ensure the sensitivity and life of the product. Be sure to power OFF the Detector before 

cleaning.  

NETWORK
TECHNOLOGIES
INCORPORATED

Tel:330-562-7070
Fax:330-562-1999

1275 Danner Dr
Aurora, OH 44202

  www.networktechinc.com

NTI

R

Clean every six months 
with a soft brush  

Note: The ENVIROMUX-SDS-CELC(P) is 
NOT intended to be used as a primary 
fire and smoke detection device.  

Summary of Contents for ENVIROMUX-SDS-CELC

Page 1: ...rary etc Product Features The detector works once connected directly to DC power A flashing LED indicates the Detector is working normally and an LED that stays ON solid indicates an alarm condition N...

Page 2: ...tal In connections in conjunction with the ENVIROMUX 16D 5D 2D add an ENVIROMUX DI16DO16 R Digital Input Output Expander See http www networktechinc com io expander html for more details Power Connect...

Page 3: ...to provide 12VDC power to sensors model ENVIROMUX SDS CELCP can be used 1 Connect the AC adapter wire labeled PLUS 12 to terminal 1 on the smoke detection sensor 2 Connect the AC adapter wire labeled...

Page 4: ...cycled in order to reset it when it goes into alert Wired using this method the smoke detector can be power cycled through the web interface when it is in alert Make sure that no sensors are configur...

Page 5: ...in to either an available RJ45 Sensor port in an ENVIROMUX 2D 5D 16D or into a pigtail wired to a Digital Input on an ENVIROMUX 2D 5D 16D No additional power supply is required The 7 foot cable can be...

Page 6: ...6 To wire your own CATx patch cable to an ENVIROMUX SDS CELC sensor follow the wiring instruction below...

Page 7: ...T intended to be used as a primary fire and smoke detection device Install Detector to Base Connect the Detector to the base Line the tab on the Detector up with the left end of the slot in the base P...

Page 8: ...ach sensor connected to the Digital In terminals on the ENVIROMUX 16D locally powered by Digital Inputs only To momentarily disrupt power to any sensor powered by a Digital Input terminal click on thi...

Page 9: ...detector When wired in this fashion make sure that none of the sensors are configured to have the output relay status change to Active Both fields below must be set to Inactive Otherwise when the rela...

Page 10: ...10 Example of sensor configuration in ENVIROMUX MINI LXO...

Page 11: ...11 Example of sensor configuration in ENVIROMUX 16D 5D 2D Example of sensor configuration in ENVIROMUX MINI...

Page 12: ...at http www networktechinc com for information regarding repairs and or returns A return authorization number is required for all repairs returns COPYRIGHT Copyright 2007 2016 by Network Technologies...

Reviews: