Replacing a fan in the services appliance
The services appliance has eight cooling fans. If one of the fans fails, you must replace it as soon
as possible to ensure that the appliance has proper cooling.
Before you begin
•
You have unpacked the replacement fan.
•
You have physically located the appliance where you are replacing the fan in the data center.
Locating the controller in a data center
•
You have confirmed that the other fans are installed and running.
•
The appliance has been placed maintenance mode.
Placing an appliance into maintenance mode
on page 78
About this task
The appliance node will not be accessible while you replace the fan.
The photograph shows a fan for the services appliance. The cooling fans are accessible after you
take the top cover off of the appliance.
Note: Each of the two power supply units also contain a fan. Those fans are not included in this
procedure.
Steps
1.
When the appliance has been placed maintenance mode, shut down the appliance.
a. Log in to the grid node:
i.
Enter the following command:
ssh admin@grid_node_IP
ii.
Enter the password listed in the
Passwords.txt
file.
iii.
Enter the following command to switch to root:
su -
iv.
Enter the password listed in the
Passwords.txt
file.
When you are logged in as root, the prompt changes from
$
to
#
.
b. Shut down the services appliance:
shutdown -h now
2.
Use one of two methods to verify that the power for the services appliance is off:
•
The power indicator LED on the front of the appliance is off.
•
The Power Control page of the BMC interface indicates that the appliance is off.
3.
Lift the latch on the top cover and remove the cover from the appliance.
4.
Locate the fan that failed.
Hardware Installation and Maintenance Guide for SG100 and SG1000 Appliances
87
Maintaining the appliance