If you have a FAS2240-2 system, a plastic flap within the now empty slot is released to cover the opening and maintain air
flow and cooling.

4. Use the cam handle to slide the power supply out of the system.

Attention: 

When removing a power supply, always use two hands to support its weight.

5. Repeat the preceding steps for any remaining power supplies.

Removing the controller module

To remove the controller module or modules from the chassis, you must perform a specific sequence of steps.

Steps

1. If you are not already grounded, properly ground yourself.

2. Unplug the system cables and SFPs from the controller module, as needed, and keep track of where the cables were

connected.

Leave the cables in the cable management arm, so that when you reinstall the cable management arm, the cables are
organized.

3. Remove the cable management arms from the left and right sides of the controller module and set them aside.

4. Squeeze the latch on the cam handle until it releases, open the cam handle fully to release the controller module from the

midplane, and then, using two hands, pull the controller module out of the chassis.

2

Replacing the chassis on a FAS22xx system

Summary of Contents for FAS22 Series

Page 1: ...g data This procedure is written with the assumption that you are moving the controller module or modules to the new chassis and that the chassis is a new component from NetApp Steps 1 Removing the po...

Page 2: ...of steps Steps 1 If you are not already grounded properly ground yourself 2 Unplug the system cables and SFPs from the controller module as needed and keep track of where the cables were connected Lea...

Page 3: ...ve the bezel from the front of the system 2 Remove the disk drives For the Then FAS2220 and FAS2240 4 systems a Press in the release button on the far left of the carrier face front 3 0TB 3 0TB 3 0TB...

Page 4: ...assis and lock the cam handle by pushing it up and against the disk drive holder Be sure to close the cam handle slowly so that it aligns correctly with the front of the drive carrier You will hear it...

Page 5: ...em cabinet or angel wings in an equipment rack 3 Slide the chassis all the way into the equipment rack or system cabinet 4 Secure the rear of the chassis to the support rail if applicable using the sc...

Page 6: ...pplies to different power sources and then turn them on 6 Press Ctrl c to stop the boot process and display the boot menu when prompted to do so and then select the option to boot to Maintenance mode...

Page 7: ...nd sldiag device status The following default response is displayed SLDIAG No log messages are present 5 Run the environmental diagnostics test by entering the following command from the Maintenance m...

Page 8: ...f or leave on the power supplies depending on how many controller modules are in the target chassis If you have two controller modules in the chassis leave the power supplies turned on to provide powe...