Hot-swapping controller power supplies
System maintenance AVA-400, AVA-800
To remove a power supply
1.
Identify the power supply you want to replace, based on the event log messages or through the amber fault LED
on the power supply.
2.
If
you
are not already grounded, properly
ground yourself
.
3.
Turn off the target power supply by turning the on/off switch to the OFF (O) position. If the power source for this
power supply has a on/off switch, turn the switch to the OFF (O) position.
4.
Remove the power cord from the power supply, using the image below as a reference.
Pinch the tab on the locking mechanism of the power cord retainer clip, and open the retainer clip.
Slide the retainer clip off the cord.
Unplug the power cord from the power supply and the power source.
5.
Press down the release latch on the power supply cam handle to unseat the power supply.
6.
Lower the cam handle to the fully open position, and then slide the power supply out of the chassis, as shown
below. Make sure that you support the power supply with your free hand.
7.
Identify power supply components as described in this table:
Component
Description
1
Power supply
2
Cam handle release latch
3
Power and fault LEDs
4
Cam handle
5
Power cord locking mechanism